Bryant FH4B Fan User Manual


 
8
SMART HEAT
* Field convertible to 1 phase.
KFAEH2501N09 is eld convertible to 3 phase.
Single point wiring kit required for these heaters in Canada.
** Blower motor heat not included.
When using units with 20-, 24-, and 30-kw electric heaters, maintain a 1-in. clearance from combustible materials to discharge plenum and ductwork,
and maintain a distance of 36 in. from the unit. Use an accessory downow base to maintain proper clearance on downow installations.
Use exible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat resistant material
for exible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and
covered with vapor barrier.
ESTIMATED SOUND POWER LEVEL (dBA)
* Estimated sound power levels have been derived using the method described in the
1987 ASHRAE HVAC Systems & Applications Handbook,
Chapter 52, p. 52.7
HEATER
PART NO.
KW
@ 240V VOLTS/PHASE
STAGES
(KW OPERATING)
INTERNAL
CIRCUIT
PROTECTION
FAN COIL SIZE
USED WITH
HEATING CAP. **
@ 230V
KFCEH0101H10 10 230/1 3, 6, 9 None 001, 002 31,400
KFCEH0201H15 15 230/1 3, 8, 11, 15 Fuse 001003 47,100
KFCEH0301H20 20 230/1 5, 10, 15, 20 Fuse 002004 62,800
UNIT
SIZE
CONDITIONS OCTAVE BAND CENTER FREQUENCY*
CFM
Ext Static
Pressure 63 125 250 500 1000 2000 4000
FH4-001 800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0
FH4-002 1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8
FH4-003 1600 0.25 69.0 65.0 61.0 58.0 56.0 54.0 50.0
FH4-004 2000 0.25 70.0 66.0 62.0 59.0 57.0 55.0 51.0