Bryant FF1DNE Fan User Manual


 
5
SPECIFICATIONS Continued
* Rated in accordance with U.S. Government DOE test procedures and/or ARI Standard 210/240-94.
Use copper wire only. Use 75°C in this application. When using non-metallic (NM) sheathed cable, wire size required should be based on that of 60°C con-
ductors, instead of wire sizes shown in table above per NEC 1996 Article 336-30. Length shown is as measured 1 way along wire path between unit and
service panel for voltage drop not to exceed 2%.
Check outdoor unit for required piston size.
†† 018 Size with 11-kw heater not approved for use with heat pumps.
UNITS WITH FACTORY-INSTALLED ELECTRIC HEATERS OR CONTROLS
UNIT SIZE 024005 024075 024011 030005 030075 030011
RATINGS & PERFORMANCES
Nominal Capacity (Btuh)* 24,000 24,000 24,000 30,000 30,000 30,000
Nominal Airow (CFM) 870 1080
Electric Heating Output (kw @240v) 5.0 7.5 11.0 5.0 7.5 11.0
Electric Heating Capacity (MBH @208/230v) 14.0/16.9 20.4/24.7 29.4/35.7 14.3/17.2 20.7/25.0 29.7/36.0
ELECTRICAL
Unit Volts-Phase (60 Hz) 208/2301 208/2301 208/2301 208/2301 208/2301 208/2301
Operating Voltage Range 187253 187253 187253 187253 187253 187253
Internal Circuit Protection None
Full Load Amps 18.1/20.0 27.1/30.0 39.8/44.0 18.1/20.0 27.1/30.0 39.8/44.0
Minimum Ampacity for Wire Sizing 24.5/26.9 35.8/39.4 51.6/56.9 25.2/27.5 36.4/40.0 52.3/57.5
Minimum Wire Size 10/10 8/8 6/6 10/10 8/8 6/6
Maximum Wire Length (Ft) 112/112 117/117 122/122 112/112 117/117 125/125
Maximum Fuse Size (Amps or Ckt Bkr) 25/30 40/40 60/60 30/30 40/40 60/60
Control Transformer 24V (Va) 40
INDOOR COIL
Rows & Fins Per In. 3 & 14
Height x Width (In.) 18 x 17.8 22 x 17.8
Face Area (Sq Ft) 2.23 2.73
R-22 Refrigerant Metering Device-FF1DNA Check-Flo-Rater
R-22 Refrigerant Metering Device-FF1DNE TXV
Piston Number 63 70
Condensate Drain Connection (Pri-Sec) 3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.) 10 x 6
Filter SizeCleanable (In.) 16 x 20 x 1
Blower Motor HP 1/5 1/3
Blower Motor Speeds & Type 2 (PSC)
Full Load Amps 1.5 2.0
OPTIONAL EQUIPMENT (P/Ns)
Louvered Wall Panel with Frame (6 Pack) KFBLG0106LGL
Electric Heat Package See ‘‘Optional Field-Installed Electric Heat Packages’’ Table