Bryant CC5A Air Conditioner User Manual


 
—5—
COOLING CAPACITIES (MBtuh)
* Saturated suction leaving evaporator coil
CFM
— Cubic Ft. per Minute
EWB —
Entering Wet Bulb (°F)
LWB
Leaving Wet Bulb (°F)
TC
Total Cooling Capacity 1000 Btuh
See notes on page 6.
UNIT
SIZE
EVAP
AIR
CFM
BF
COIL REFRIGERANT TEMPERATURE* (°F)
35 40 45 50 55
Evaporator Air — Entering Wet Bulb Temperature (°F)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
A018
450 22 27 34 18 24 30 14 20 26 11 16 22 9 11 18
0.17 15 15 14 14 13 13 12 12 11 10 10 9888
600 26 33 41 22 29 37 18 24 32 14 19 27 12 13 21
0.22 19 18 17 17 16 15 15 14 13 12 12 11 10 10 10
750 30 38 47 25 33 42 20 28 37 17 22 30 14 15 24
0.25 22 21 20 20 19 17 17 17 15 14 14 13 11 12 11
A024
W024
600 28 36 44 24 31 39 19 26 34 15 21 29 13 15 23
0.12 20 20 18 18 17 16 16 15 14 13 13 12 11 11 10
800 34 43 52 29 37 47 23 32 41 19 25 35 16 18 27
0.16 25 24 22 22 21 20 19 19 17 16 16 15 13 14 13
1000 39 49 60 33 43 54 27 36 47 22 29 39 19 20 31
0.18 29 27 25 26 25 23 23 22 20 19 19 17 16 16 15
A030
W030
750 37 46 57 31 41 52 25 34 45 19 27 38 14 16 25
0.13 26 25 24 24 23 22 21 20 19 17 17 16 14 14 13
1000 45 57 70 38 50 63 30 42 55 25 33 46 17 19 30
0.17 33 31 29 29 28 26 26 25 23 21 22 20 17 18 16
1250 52 66 81 44 57 73 35 48 63 29 38 53 20 22 34
0.20 39 36 34 35 23 30 30 29 27 25 25 23 20 21 19
A036
W036
900 42 52 63 35 46 57 28 39 50 22 31 42 19 22 33
0.10 34 32 30 30 29 27 27 26 24 22 22 21 19 19 18
1200 50 62 75 43 55 68 34 46 60 28 37 50 23 26 40
0.13 41 39 35 38 35 32 33 32 29 28 28 25 23 23 22
1500 57 70 84 49 62 76 39 52 67 33 42 57 27 30 45
0.16 48 44 40 44 41 37 39 37 33 33 33 29 27 28 25
A042
W042
1050 45 56 68 38 49 61 31 41 54 25 33 45 20 23 36
0.14 37 54 32 33 31 29 29 28 26 25 24 23 20 21 19
1400 53 66 79 45 58 72 36 49 63 31 39 53 25 26 42
0.17 45 41 37 41 38 34 36 34 31 31 30 27 25 28 23
1750 60 73 87 51 65 80 42 55 70 36 44 60 30 32 47
0.20 52 47 42 47 44 38 42 40 35 36 35 31 30 30 27
A048
W048
1200 48 59 71 41 52 64 33 44 57 30 36 49 22 26 39
0.18 39 36 33 36 34 30 32 30 28 30 27 24 22 23 21
1600 55 68 80 47 60 74 39 51 66 33 41 56 27 30 45
0.22 47 43 38 43 40 35 38 36 32 33 32 29 27 28 25
2000 61 74 88 53 66 81 44 57 72 38 46 62 32 34 50
0.25 54 49 42 50 45 39 44 42 36 38 37 33 32 32 29
C048
1200 44 57 69 36 48 62 30 40 53 25 29 43 20 21 32
0.11 39 36 33 35 33 30 30 29 27 25 25 23 20 21 19
1600 52 65 78 43 56 71 37 46 61 31 35 50 25 25 37
0.15 48 44 38 42 40 35 37 36 32 31 31 28 25 25 24
2000 57 71 85 49 62 78 42 50 68 36 39 55 29 29 41
0.19 55 50 42 49 46 40 42 41 36 36 37 32 29 29 27
A060
1600 57 71 87 48 62 78 38 52 68 31 41 57 26 29 44
0.22 47 44 41 43 40 37 37 36 33 31 31 29 26 26 24
2000 65 80 97 54 70 88 43 59 76 36 46 64 30 33 50
0.25 55 51 46 50 46 42 43 42 38 36 37 33 30 31 28
2400 71 88 105 60 77 95 48 65 83 41 51 70 34 36 55
0.28 62 57 50 56 52 46 48 47 42 41 41 37 34 34 31
W060
1600 63 78 94 54 69 85 43 59 75 35 47 64 29 34 51
0.16 52 48 44 47 44 40 41 40 36 35 35 32 29 29 27
2000 71 88 105 61 78 96 49 66 85 41 53 72 34 39 58
0.19 60 55 50 55 51 46 48 46 42 41 41 37 34 34 32
2400 78 96 114 67 85 104 55 73 93 46 58 79 39 43 64
0.21 68 62 54 62 57 51 54 52 46 46 46 41 39 39 36
BF
Bypass Factor
MBH
1000 Btuh
SHC
— Sensible Heat Capacities (1000 Btuh) shown in
Italic
type. SHC is based on 80°F db temper-
ature of air entering the evaporator coil. Below 80°F db, subtract (corr factor x cfm) from SHC.
Above 80°F db, add (correction factor x cfm) to SHC.