VERTICAL ECONOMIZER
(FACTORY INSTALLED OPTION)
GENERAL
Economizers are recommended for only commercial packaged
products that have X13 motors. The Economizer system utilizes
the latest technology available for integrating the use of free
cooling with mechanical cooling for rooftop units. The solid state
control system optimizes energy consumption, zone comfort, and
equipment cycling by operating the compressors when the outdoor
air temperature is too warm, integrating the compressor with
outdoor air when free cooling is available, and locking out the
compressor when outdoor air temperature is too cold. Demand
ventilation is supported.
The Economizer system utilizes gear--drive technology with a
direct --mount spring return actuator that will close upon loss of
power. The Economizer system comesstandard with an outdoor air
temperature sensor, a supply air temperature sensor, and low
temperature compressor lockout switch. Indoor enthalpy, outdoor
enthalpy, and CO
2
sensors are available for field installation.
Barometric relief dampers provide natural building pressurization
control. Barometric relief dampers are built into the design and are
standard. See Table 10 for Hood Package contents. See Table 11
forsensorusage.
Table 10 – PackageContents
SMALL CHASSIS
(Sizes 30 and 36)
LARGE CHASSIS
(Sizes 42, 48, and 60)
Qty Content Description Qty Content Description
1 HoodSide, Right 1 HoodSide, Right
1 Hood Side, Left 1 Hood Side, Left
2 Angle, Filter 2 Angle, Filter
1
Aluminum Filter
(20---1/2” x 16---1/2 x 1”)
(521 x419 x 25 mm)
1
Aluminum Filter
(20---1/2” x 16---1/2 x 1”)
(521 x419 x 25 mm)
18
Screws
(#10 --- 14 x 5/8” w/Seal
Washer)
18
Screws
(#10 --- 14 x 5/8” w/Seal
Washer)
2
Screws
(#8 --- 18 x 3/4” Type B Pan
Head)
2
Screws
(#8 --- 18 x 3/4” Type B Pan
Head)
1 Bracket,Sensor
Table 11 – Economizer SensorUsage
APPLICATION
ECONOMIZER WITH OUTDOOR AIR DRY BULB
SENSOR
Accessories Required
Outdoor Air Dry Bulb
None,Theoutdoorairdrybulbsensorisfactory
installed.
SingleEnthalpy HH57AC078
Differential Enthalpy HH57AC078andCRENTDIF004A00*
CO
2
for DCV Control
Using a Wall ---Mounted
CO
2
Sensor
33ZCSENC02 or CGCDXSEN004A00
CO
2
for DCV Control
Using a Duct---
Mounted CO
2
Sensor
33ZCSENC02 or
CGCDXSEN004A00{
and 33ZCASPCO2 or
CGCDXASP00100**
or CRCBDIOX005A00{{
*CRENTDIF004A00accessory is usedon man y different baseunits.As
such, these kits may contain parts that will not be needed for installation.
{33ZC S ENCO2 and CGCDXS EN004A00 are accessory CO
2
sensors.
**33ZCASPC02 AND CGCD XASP00100 are accessory aspirator boxes
required forduct---mountedapplications.
{{CRCBDIOX005A00 isan accessory that contains both 33ZCSENCO2
AND 33ZVASPC02 accessories.
ACCESSORIES
The economizer has several field--installed accessories available to
optimize performance. Refer to Table 12 for authorized parts.
Table 12 – Accessory List
DESCRIPTION PART NUMBER
Outdoor AirEnthalpySensor HH57AC078
Indoor AirEnthalpy Sensor CRENTDIF004A00
ReturnAir CO
2
Sensor (4---20 mA) CRCBDIOX005A00
CO
2
Room Sensor (4---20 mA)
33ZCSENX02 Or
CGCDXSEN004A00
AspiratorBox for duct MountCO
2
Sensor
(4 --- 20 mA)
33ZCASPC02 Or
CGCDXASP001A00
Space Temperature andCO
2
Room
Sensor with Override (4---20mA)
33ZCT55C02
Space Temperature andCO
2
Room
Sensor with Override andSet Point
(4 --- 20mA)
33ZCT56C02
Heat PumpRelay Package CPRLYKIT001A00
INSTALLATION
Small Chassis
To install the Vertical Economizer on the small ch assis perform the
following procedure:
1. Turn off unit power supply and install lockout tag.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, a lways turn off main
power to system and install lockout tag. There may be more
than one disconnect switch. Turn off accessory heater
power switch if applicable.
!
WARNING
2. Remove economizer hood top panel from the return side of
the unit. See Fig. 22. Keep screws and panel next to the
unit.
3. Open economizer hood package found on the top skid.
4. Remove red shipping tape that attaches the outside air
temperature (OAT) sensor to the economizer assembly.
Using two #8 fasteners, found in the hood package, attach
the OAT sensor to the economizer according to Fig. 23.
NOTE: See label attached to economizer for OAT installing
details.
5. Remove horizontal return duct cover panel and cut the wire
ties that hold the hood divider to the economizer assembly.
Slide hood divider off from the two slots holding it in place
and place next to the unit. See Fig. 24.
604D-- --A