Bryant 566D Air Conditioner User Manual


 
77
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
LEGEND
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
HEATER PART NO. UNIT V-PH-Hz
FAN MOTOR
ELECTRIC HEATER(S)
MCA* MOCP*
Nominal
Capacity (kW)
Actual Capacity (kW) FLA
Hp kW FLA Stage 1 Stage 2 Total
CAELHEAT025A00
524A-B180,240
524A-C180,240
208-3-60
3.7 2.76 10.2 50 22.6 15.0 37.6 104.3 143.1 150
5.0 3.73 14.6 50 22.6 15.0 37.6 104.3 148.6 150
7.5 5.59 21.5 50 22.6 15.0 37.6 104.3 157.2 175
240-3-60
3.7 2.76 10.2 50 30.0 20.0 50.0 120.3 163.1 175
5.0 3.73 12.8 50 30.0 20.0 50.0 120.3 166.4 175
7.5 5.59 19.4 50 30.0 20.0 50.0 120.3 174.6 200
CAELHEAT026A00 480-3-60
3.7 2.76 4.8 50 30.0 20.0 50.0 60.1 81.2 90
5.0 3.73 6.4 50 30.0 20.0 50.0 60.1 83.2 90
7.5 5.59 9.7 50 30.0 20.0 50.0 60.1 87.3 90
CAELHEAT027A00 575-3-60
3.0 2.24 3.8 50 30.0 20.0 50.0 50.2 67.5 70
5.0 3.73 5.1 50 30.0 20.0 50.0 50.2 69.1 70
7.5 5.59 7.8 50 30.0 20.0 50.0 50.2 72.5 80
CAELHEAT028A00
524A-B300
524A-C300
208-3-60
7.5 5.59 19.8 20 14.9 14.9 41.5 78.7 80
10.0 7.46 28.2 20 14.9 14.9 41.5 87.1 100
240-3-60
7.5 5.59 19.4 20 19.9 19.9 47.9 81.4 90
10.0 7.46 26.8 20 19.9 19.9 47.9 93.3 110
CAELHEAT029A00 480-3-60
7.5 5.59 9.7 20 20.0 20.0 24.1 42.2 50
10.0 7.46 13.4 20 20.0 20.0 24.1 46.8 50
CAELHEAT030A00 575-3-60
7.5 5.59 7.8 20 20.0 20.0 20.1 34.9 35
10.0 7.46 10.3 20 20.0 20.0 20.1 38.0 40
CAELHEAT031A00
208-3-60
7.5 5.59 19.8 40 15.0 15.0 30.0 83.4 131.1 150
10.0 7.46 28.0 40 15.0 15.0 30.0 83.4 139.5 150
240-3-60
7.5 5.59 19.4 40 20.0 20.0 40.0 96.2 144.5 150
10.0 7.46 26.8 40 20.0 20.0 40.0 96.2 153.8 175
CAELHEAT032A00 480-3-60
7.5 5.59 9.7 40 20.0 20.0 40.0 47.9 71.9 80
10.0 7.46 13.4 40 20.0 20.0 40.0 47.9 76.6 80
CAELHEAT033A00 575-3-60
7.5 5.59 7.8 40 20.0 20.0 40.0 40.2 60.0 60
10.0 7.46 10.3 40 20.0 20.0 40.0 40.2 63.1 70
FLA Full Load Amps
Hp Horsepower
MCA Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection (Amps)
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1
480 0.694 0.84 0.918 1
575 0.915 1 1.089
50TFQ004-012
524A072-300