DETAILED COOLING CAPACITIES* Continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.
** Unit kw is outdoor unit kilowatts only.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
‡‡ Data are with FC4 and FK4 R-22 TXV replaced with Puron® TXV.
EVAP
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**
Capacity
MBtuh†
Total
Sys
Kw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
533AN060-A Outdoor Section With CK5AA060 Indoor Section
1600
72 67.5 32.8 4.50 64.6 31.8 4.99 61.6 30.7 5.54 58.3 29.5 6.14 54.8 28.3 6.81 50.8 26.9 7.57
67 62.8 41.9 4.44 59.7 40.6 4.91 56.7 39.4 5.45 53.3 38.0 6.06 49.9 36.7 6.71 44.2 34.5 7.42
63†† 55.5 39.5 4.32 51.6 37.8 4.77 47.6 36.0 5.27 45.3 35.1 5.88 42.7 33.9 6.55 39.1 32.5 7.28
62 54.2 48.8 4.30 50.5 47.1 4.75 46.7 45.2 5.26 44.5 44.1 5.86 42.7 42.7 6.55 40.2 40.2 7.30
57 50.9 50.9 4.25 47.8 47.8 4.70 46.1 46.1 5.25 44.2 44.2 5.85 42.4 42.4 6.54 40.4 40.4 7.30
1800
72 68.2 33.7 4.58 65.4 32.8 5.08 62.4 31.7 5.63 59.0 30.6 6.24 55.4 29.4 6.91 51.3 28.1 7.66
67 63.8 43.9 4.52 60.8 42.8 5.01 57.4 41.4 5.54 54.1 40.1 6.15 50.5 38.8 6.82 44.8 36.6 7.52
63†† 56.6 41.6 4.41 52.6 39.9 4.87 50.4 39.0 5.41 48.0 38.0 6.01 45.4 36.8 6.69 39.9 34.6 7.38
62 55.5 51.9 4.40 51.8 50.1 4.85 49.7 49.1 5.39 47.7 47.7 6.01 45.8 45.8 6.70 41.7 41.7 7.43
57 52.9 52.9 4.36 51.2 51.2 4.84 49.4 49.4 5.38 47.4 47.4 6.00 45.6 45.6 6.70 41.9 41.9 7.43
2000
72 68.8 34.6 4.67 66.0 33.7 5.16 62.9 32.7 5.72 59.5 31.7 6.33 55.8 30.5 7.00 51.7 29.2 7.75
67 64.4 45.6 4.60 61.5 44.6 5.09 58.0 43.2 5.62 54.7 42.1 6.23 51.1 40.9 6.91 45.8 38.9 7.62
63†† 57.6 43.6 4.51 53.9 42.1 4.96 52.9 41.7 5.53 50.5 40.7 6.14 45.6 38.7 6.78 40.5 36.6 7.47
62 56.8 54.9 4.49 54.7 53.9 4.97 52.5 52.5 5.52 50.5 50.5 6.15 47.8 47.8 6.82 43.0 43.0 7.55
57 56.1 56.1 4.48 54.1 54.1 4.97 52.3 52.3 5.52 50.3 50.3 6.14 47.8 47.8 6.82 43.1 43.1 7.55
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
CC5A/CD5AA 060 0.95 0.98 FX4ANB 060 0.97 1.01
CC5A/CD5AW 060 1.00 1.00
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CE3AA 060 0.98 1.00 CC5A/CD5AA 060 0.97 0.96
CK3BA 060 0.98 1.00 CC5A/CD5AW 060 1.00 0.96
CK5A/CK5BA 060 1.00 1.00 CK3BA 060 1.00 0.96
CK5A/CK5BT 060 0.98 1.00 CK5A/CK5BA 060 1.00 0.96
CK5A/CK5BX 060 1.00 1.00 CK5A/CK5BX 060 1.00 0.96
F(A,B)4AN(F,B,C) 060 0.98 1.04
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
FB4ANB 070 1.00 1.02 CC5A/CD5AA 060 0.97 0.97
FC4BN(F,B) 060 0.98 1.03 CC5A/CD5AW 060 1.00 0.96
FC4BNB 070 1.00 1.01 CK3BA 060 1.00 0.97
FG3AAA 060 0.97 1.00 CK5A/CK5BA 060 1.00 0.97
FK4CNB 006 1.00 0.95 CK5A/CK5BX 060 1.00 0.97
FV4ANB 006 1.00 0.95