Indirect Heater Specifications
Heater Model
Output
Series Number
BTU/HR
80°-140° 60°-140° 40°-140° 40°-160°
DR SERIES DR/F-350-WT 280,000 559 420 336
(Forced Draft)
DR/F-450-WT 360,000 720 540 432
F SERIES DR/F-650-WT 520,000 1,039 780 624
(Atmospheric)
DR/F-850-WT 680,000 1,359 1,020 816
CLM SERIES CLM-120-WT 960,000 1,920 1,440 1,152 960
(Forced Draft)
CLM-150-WT 1,200,000 2,400 1,800 1,440 1,200
&
CLM-180-WT 1,440,000 2,880 2,160 1,728 1,440
(Atmospheric)
CLM-210-WT 1,680,000 3,660 2,520 2,016 1,680
CLM-240-WT 1,920,000 3,840 2,880 2,304 1,920
CLM-270-WT 2,160,000 4,320 3,240 2,592 2,160
CLM-300-WT 2,400,000 4,800 3,600 2,880 2,400
K SERIES K-350-WT 2,800,000 5,600 4,200 3,360 2,800
(Atmospheric)
K-400-WT 3,200,000 6,400 4,800 3,840 3,200
K-450-WT 3,600,000 7,200 5,400 4,320 3,600
K-500-WT † 4,000,000 8,000 6,000 4,800 4,000
K-550-WT † 4,400,000 8,800 6,600 5,280 4,400
K-600-WT † 4,800,000 9,600 7,200 5,760 4,800
K-650-WT † 5,200,000 10,400 7,800 6,240 5,200
AB SERIES AB-90-WT 720,000 1,440 1,080 864 720
(Forced Draft)
AB-120-WT 960,000 1,920 1,440 1,152 960
AB-150-WT 1,200,000 2,400 1,800 1,440 1,200
AB-200-WT 1,680,000 3,360 2,520 2,016 1,680
AB-250-WT 2,000,000 4,000 3,000 2,400 1,999
AB-300-WT 2,400,000 4,800 3,600 2,880 2,400
RV SERIES RV-350-WT 2,800,000 5,600 4,200 3,360 2,800
(Forced Draft)
RV-400-WT 3,200,000 6,400 4,800 3,840 3,200
RV-450-WT 3,600,000 7,200 5,400 4,320 3,600
RV-500-WT † 4,000,000 8,000 6,000 4,800 4,000
RV-550-WT † 4,400,000 8,800 6,600 4,280 4,400
RV-600-WT † 4,800,000 9,600 7,200 5,760 4,800
RV-700-WT † 5,600,000 11,200 8,400 6,720 5,600
RV-800-WT † 6,400,000 12,800 9,600 7,680 6,400
Bryan Steam LLC Leaders Since 1916
783 N. Chili Ave., Peru, Indiana 46970 U.S.A.
Phone:765-473-6651
Internet:www.bryanboilers.com
Fax: 765-473-3074
E-mail:bryanboilers@iquest.net
Water-Pak Selection
Water-Pak units are built to furnish a very wide selection of
recovery rates, storage capacities and configurations. Both
horizontal and vertical tanks are available to best fit into the
space allocation. In addition to the combinations of "settings"
shown below, other combinations, arrangements and sizes
are possible. Fuel selection includes gas (atmospheric or
forced draft), oil, gas-oil or electric (consult factory).
1. Select Heater Model based on "Heater Specifications" table
below.
2. Select storage capacity from "Storage Tank Specifications"
tables, horizontal or vertical tank depending on space
considerations.
3. Choose appropriate "Setting" from "Heater, Tank Setting"
diagrams on previous page.
Selection Procedure Example
A requirement of 800 gph at 100° rise. Storage capacity 1000
gallons. Fuel, gas. Tank lining, cement.
1. From "Heater Specifications" table, select Model No. CLM-
120-WT Gas, rated at 1,152 gph, 40° to 140° rise.
2. From the "Storage Tank Specifications" tables, suppose
you select the 1045 gallon horizontal tank.
3. Then the setting shown in diagram "AH" (horizontal tank)
would be appropriate.
Specify:Specify:
Specify:Specify:
Specify:
Water-Pak System CLM-120-WT - G - 1045 - AH - CM - IN
Storage Tank Specifications
Tank Tank Approximate
Capacity Dia × Length Weight
gallons in (cm) lbs (Kg)
Horizontal Tanks
H-387 36×96 (91.4×243.8) 2,000 (907)
H-520 42×96 (106.7×243.8) 2,200 (998)
H-802 42×144 (106.7×365.8) 3,000 (1,361)
H-1045 48×144 (121.9×365.8) 3,800 (1,724)
H-1546 54×168 (137.2×426.7) 5,600 (2,540)
H-2188 60×192 (152.4×487.7) 6,900 (3,130)
H-2699 72×168 (182.9×426.7) 8,100 (3,674)
H-3533 72×216 (182.9×548.6) 10,100 (4,581)
Vertical Tanks
V-335 36×84 (91.40×213.4) 1,700 (771)
V-520 42×96 (106.7×243.8) 2,200 (998)
V-665 48×96 (121.9×243.8) 2,700 (1,225)
V-844 54×96 (137.2×243.8) 3,100 (1,406)
V-1030 60×96 (152.4×243.8) 4,000 (1,814)
V-1447 72×96 (182.9×243.8) 5,300 (2,404)
V-1922 84×96 (213.4×243.8) 7,000 (3,175)
FuelFuel
FuelFuel
Fuel
G—gas
O—oil
GO—gas-oil
StorageStorage
StorageStorage
Storage
SectionSection
SectionSection
Section
SizeSize
SizeSize
Size
(gals.)
TankTank
TankTank
Tank
InsulatedInsulated
InsulatedInsulated
Insulated
PVCPVC
PVCPVC
PVC
JacketJacket
JacketJacket
Jacket
IndirectIndirect
IndirectIndirect
Indirect
HeaterHeater
HeaterHeater
Heater
ModelModel
ModelModel
Model
SettingSetting
SettingSetting
Setting
Tank LiningTank Lining
Tank LiningTank Lining
Tank Lining
CM—cement
PH—phenolic
Gallons Per Hour*
Heater Capacity
These units are equipped with two heat exchangers as standard and require a copper header to be field supplied.
*
Note 1: Contact factory for ratings at other conditions.
Note 2: Heater is not intended to provide the temperature increases shown above instantly, but will raise the
temperature of the gallons listed to final storage temperature within one hour.
Note 3: Select adequate storage tank capacity to handle peak demand. Keep in mind that, typically, only 75%
of tank capacity is usable storage.