Sensible Apparent Latent Recovery
Supply Net Average Recovery Sensible Moisture
Temperature Airflow Power Efficiency Effectiveness Transfer
Heating C F L/s cfm Watts % %
0 32 30 64 54 75 83 -0.03
0 32 46 97 78 67 74 0.01
0 32 65 138 124 64 72 -0.02
-25
-13 26 55 62 67 89 0.05
Total Recovery Efficiency
Cooli
ng 35 95 Not Tested
Voltage: 120 V AC
Frequency: 60Hz
Dimensions: 21.1 x 34.6 x 13.25
Weight: 65 lbs
Shipping Weight: 75 lbs
Warranty: 2 years, parts
HVI Rated of air flow: 169 CFM
P
ower Consumed (max): 150 Watts
Supply air duct connections: 6" Diameter
Exhaust air duct connections: 6" Diameter
Filter: 30 ppi washable reticulated foam
Cabinet: 20 ga. Pre-painted steel
Mounting: Suspension by chains and springs
Wall control modes: N/A
Power: 147 Watts
Current: 1.4 Amps
HRV100H Specifications
Ventilation Performance
External Static Net Supply Gross Airflow
Pressure Airflow Supply Exhaust
Pa In.W.g. L/s cfm L/s cfm L/s cfm
25 0.1 84 177 88 186 90 190
50 0.2 80 169 84 178 86 182
75 0.3 77 163 81 171 81 171
100 0.4 69 146 72 153 76 161
125 0.5 61 130 65 137 66 139
150 0.6 46 98 49 103 52 110
175 0.7 38 81 40 85 31 67
Distributed By
Installation
Options
Energy Performance
©2005 Broan-NuTone, LLC 9985 0753A 7/05
www.Broan.com
Broan-NuTone, LLC, 926 W. State Street,Hartford,WI 53027 • 800-558-1711
In Canada call 888-882-7626
Return Connection — Extended Exhaust Fully Ducted SystemReturn-Return Connection
B
A