Breckwell P2700 Heating System User Manual


 
COMBUSTION AIR SUPPLY
For a mobile home installation the stove must be
connected to an outside source of combustion air. A 2”
inside diameter metallic pipe, either flexible or rigid, may
be attached to the inlet at the stove’s rear (refer to figure
4). A rodent guard (minimum ¼” wire mesh)/wind hood
must be used at the terminus (refer to figure 5). All
connections must be secured and airtight by either using
the appropriately sized hose clamp and/or UL-181-AP
foil tape.
For mobile home installations only: 2” inside diameter
pipe may be used for the first 5 feet of combustion air
supply run. From 5 to 10 feet use 2 ¾” inside diameter
pipe. No combustion air supply may exceed 10 feet.
Sources of Outside Combustion Air
a. In fireplaces
Chimney top.
Ash clean out door.
b. For freestanding installations
A hole in floor near stove rear terminating only
in a ventilated crawl space.
A hole in the wall behind the stove.
WHEN OUTSIDE AIR IS NOT USED
If outside air is not used, it is important that combustion
air is easily available to the air inlet. A closeable outside
air register can be used in tightly insulated homes.
VENTING
The Breckwell P2700 is certified for use with listed
TYPE L-Vent, 3” or 4” diameter in size. The stove was
tested with Simpson Duravent brand. Class “A” chimney
is not required. Refer to the instructions provided by the
vent manufacturer, especially when passing through a
wall, ceiling or roof.
This is a pressurized exhaust system. All vent connector
joints must be sealed with 500°F (260°C) RTV silicone
sealant to ensure consistent performance and avoid
smoke spillage. All horizontal connector joints must be
sealed with UL-181-AP foil tape. We recommend that all
vertical vent connector joints be secured with a minimum
of 3 screws.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
DO NOT INSTALL A FLUE DAMPER IN THE
EXHAUST VENTING SYSTEM OF THIS UNIT.
INSTALL VENT AT CLEARANCES SPECIFIED BY
THE VENT MANUFACTURER.
INSTALLATION
9
FIGURE 4
FIGURE 5
INSTALLATION
6