Bosch Appliances LTC 8714 Home Security System User Manual


 
EN
|
8
Bosch Security Systems | May 23, 2005
LTC 8714 and 8715 Series | Instruction Manual | Installation
4.4.1 DIP Switch Settings - LTC 8714 Series
S401 DIP Switch: Verify that switches 1, 2, and 3
are ON and all others are OFF.
S402 DIP Switches 1 to 5: Baud rate and poll type
settings must match those on the Allegiant Series
keyboards. Group number should be selected to agree
with capacity and configuration settings associated with
specific Allegiant series system being used.
S402 DIP Switches 6 to 8: These switches determine
the data polling format that will be used to
communicate with the keyboards. The 4 Poll selection
would typically be used only in LTC 8600 Series
systems using fixed speed receiver/driver equipped
cameras. The 8 Poll selection would typically be used
in LTC 8800 and LTC 8900 systems with fixed speed
receiver/drivers. The 6 Poll selection should be used in
any system where Allegiant Series keyboards are being
used to control variable speed AutoDome
®
Series
cameras.
4.4.2 DIP Switch Settings - LTC 8715 Series
S401 DIP Switch: Verify that switches 1, 2, and 3 are
ON and all others are OFF.
S402 DIP Switch: Verify that switches 1, 2, and 3 are
ON and all others are OFF if the LTC 8715 will have
LTC 8714 units connected directly to it. Verify that
switches 1, 2, 3, and 5 are ON and all others are OFF
if the LTC 8715 will have other LTC 8715 units
connected directly to it (see FIGURE 11).
Switch Number Function
1 Allegiant Keyboard
Baud Rate
OFF 9600 (Factory Default
Setting)
ON 19200
2345 Group Number
OFFOFF OFFOFF 0 (Kbd 1–8)
OFFOFF OFFON1 (Kbd 9–16)
(Factory Default
Setting)
OFFOFF ON OFF2 (Kbd 17–24)
OFFOFF ON ON 3 (Kbd 25–32)
OFFONOFF OFF4 (Kbd 33–40)
OFFONOFF ON 5 (Kbd 41–48)
OFFONONOFF 6 (Kbd 49–56)
OFFONONON7 (Kbd 57–64)
ON OFFOFF OFF8 (Kbd 65–72)
ON OFFOFF ON 9 (Kbd 73–80)
ON OFFONOFF 10 (Kbd 81–88)
ON OFFONON11 (Kbd 89–96)
ON ON OFFOFF 12 (Kbd 97–104)
ON ON OFFON13 (Kbd 105–112)
ON ON ON OFF14 (Kbd 113–120)
ON ON ON ON Reserved
Switch Number
67Poll Type
OFF OFF 4 POLL
OFF ON 8 POLL
ON OFF 6 POLL
(Factory Default Setting)
ON ON Reserved
8Reserved