Bosch Appliances FMC210SM Smoke Alarm User Manual


 
2 | FMC‑210‑SM Single Action Call Points
The maximum number of LSN elements that may be
connected depends on their current consumption
from the LSN data line. The limit values should be
taken from the product information supplied with the
fire panel used.
Further standards, guidelines and planning
recommendations regarding the installation location
etc., should also be taken into consideration (see Fire
Detection manual).
The regulations of the local fire services must be
observed.
Installation notes in accordance with VdS/VDE
The distance between manual call points should not
be more than 100 m according to DIN 14675 or 80 m
according to VdS.
In high risk areas, manual call points should be
installed at a distance of max. 40 m (VDE 0833 Part 2,
Point 7.2.6).
Installation
The cable duct can be surface-mounted or flush-
mounted.
Installation in fire hose cabinets is possible in three
ways:
135 mm
140 mm
2,5 mm
2 mm
139 mm
1
2
3
149,5 mm
12,5 mm
Pos. Description
1 Installation depth version 1: ca. 40 mm
2 Installation depth version 2: 14 mm
3 Installation depth version 3: min. 30 mm
Parts Included
TypeNumber. Component
FMC‑210‑SM‑G‑B
Form G, Blue
Single Action Call Point for indoor use, direct trig-
gering (type A)
FMC‑210‑SM‑G‑R
Form G, Red
Single Action Call Point for indoor use, direct trig-
gering (type A
Note The key must be ordered separately.
Technical Specifications
Electrical
Operating voltage 15 V DC . . . 33 V DC
Current consumption 0.4 mA
Mechanics
Dimensions (H x W x D) 135 x 135 x 40 mm
Housing material Plastic, ASA
Colors
FMC-210-SM-G-R
Red, RAL 3001
FMC-210-SM-G-B
Blue, RAL 5005
Weight Approx. 235 g