Fire Alarm Systems | FMC‑210‑SM Single Action Call Points
The FMC‑210‑SM Single Action Call Points are used for
manual triggering, and can be used in the Local
SecurityNetwork LSN and LSN improved. The
FMC‑210‑SM Single Action Call Points are designed for
indoor deployment.
Functions
1 1
2
23
3
4
5
With single action call points, the alarm is triggered when
the glass plate (2) is broken and the button (3) springs
up.
This activates the microswitch for alarm triggering and the
indicator LED (4) blinks.
The call point (3) can be reset after inserting a new glass
pane (2) and closing the door of the single action call
point (1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Individual call point identification with display of the call
point address on the fire panel ensures the quick location
of the triggered call point.
Certifications and Approvals
FMC‑210‑SM‑G‑R applies to
EN 54‑11:2001/A1:2005
EN 54‑17:2005
Region Certification
Germany VdS G 207008 FMC-210-SM-G-R
Europe CPD 0786-CPD-20316 FMC-210-SM-G-R
Installation/Configuration Notes
Manual call points must be mounted visibly along
escape and rescue routes (e. g. exits, passageways,
stairwells) and be easily accessible.
An installation height of 1400 mm ±200 mm, measured
from the middle of the manual call point to the floor,
must be maintained.
Manual call points must be adequately illuminated by
sunlight or another light source (including emergency
lighting if present).
FMC‑210‑SM Single Action Call Points
Alarm triggering by breaking of the glass pane
Automatic or manual detector addressing via rotary
switch possible
Indicator LED for alarm or for inspection evaluation
Call point query routines with evaluation and multiple
transmission
Individual call point identification
Maintains LSN loop functions in the event of wire
interruption or short-circuit thanks to two integrated
isolators