Bosch Appliances FMC-120-DKM Smoke Alarm User Manual


 
Region Certification
PTB 01 ATEX 2163 X OTC/OC 310/410,
OT/O/T 300/400, DKM/SKM 120, DM/
SM 210, MPA_01 ATEX 2163 X
PTB 01 ATEX 2163 X FMC-120-DKM
Europe CE FMC-120-EST-G-B / -DKM-G-Y
CE FMC-120-DKM-G-R/-H-R
CE FMC-120-DKM-G-B/ -H-B
CPD 0786-CPD-20294 FMC-120-DKM-G/H-
R
CPD 0786-CPD-20231 FMC-120-DKM-G-Y
CPD 0786-CPD-20232 FMC-120-EST-G-B/-
H-HE
Installation/Configuration Notes
Manual call points have to be mounted visibly along
escape and rescue routes (e.g. exits, passageways,
stairwells) and be easily accessible.
An installation height of 1400 mm ±200 mm, meas-
ured from the middle of the manual call point to the
floor, must be maintained.
Manual call points must be illuminated sufficiently
with daylight or another light source (including emer-
gency lighting, if present).
Max. one test detector may be used for primary lines
together with automatic detectors. The test detector
is connected at the end of the primary line.
Further standards, guidelines and planning recom-
mendations regarding the installation location etc.,
should also be taken into consideration (see Fire De-
tection manual).
Regulations of local fire departments must be ob-
served.
Installation
Cables can be inserted surface-mounted or flush-
mounted.
ø 3,4
Installation in fire hose cabinets is possible in three
ways:
135°
140°
2,5
2
139
1
2
3
10
147
Pos. Description
1 Installation depth version 1: 36 mm
2 Installation depth version 2: 14 mm
3 Installation depth version 3: approx. 30 mm
Technical Specifications
Electrical
Operating voltage 24 V DC (16.2 V DC . . . 30 V DC)
Current consumption Specified by the respective se-
curity system
Mechanics
Dimensions (W x H x D) 135 x 135 x 37 mm /
5.31 x 5.31 x 1.4 in.
Housing material Plastic (ASA)
Colors Red, RAL 3001
Blue, RAL 5005
Yellow, RAL 1003
Weight Approx. 224 g
2 | FMC‑120‑DKM Manual Call Points