2 | FLM‑325‑IM Contact Module
Data Circuit Length
Data (or polling) circuit length is the distance over the
circuit wire from the connection at the FACP to the most
distant device and back to the FACP. Data circuit length
must include the distance to any device connected to the
circuit in a T tap. The screw terminals can accept up to 14
AWG (1.5 mm) wire, but this reduces the allowable length
of the circuit.
Refer to the FPE‑1000‑SLC Installation Guide
(P/N: F01U078099) for specific wire instructions and
specifications for the FPA‑1000 series panels.
Initiating Device Circuit Connections
The initiating device circuit can use any number of UL-
listed normally open (NO) contact closure devices. Device
circuit wiring must not exceed 50 Ω. Install contact
closure devices according to the manufacturer’s
installation instructions. All wiring must be supervised and
power-limited.
Note Do not mix fire alarm initiating and
supervisory devices on the same module.
Parts Included
Quant. Component
1 Point contact module
1 EOL resistor: Hochiki P/N 0400‑01046,. 10 kΩ, ¼ W, ¼ in.
1 Literature – Installation Guide
Technical Specifications
Electrical
SLC Applied Voltage (rated range): 25.3 VDC to 39 VDC
SLC Current Consumption: Standby: 0.339 mA
Alarm: 0.358 mA
Resistance
End of Line Device 10 kΩ, 0.25 W per resistor
Initiating Device Circuit Less than 50 Ω
Environmental
Environment: Indoor dry
Relative Humidity: Up to 90%, non‑condensing
Temperature: Operating: 0°C to +49°C (+32°F to +120°F)
Storage: -30°C to +70°C (-22°F to +158°F)
Mechanical
Dimensions (H x W x D) 2.375 in. x 1.75 in. x 0.5 in.
(60.325 mm x 44.45 mm x 12.7 mm)
Weight 20 oz (0.567 kg)
Trademarks
Trademark names are used throughout this document. In
most cases, these designations are claimed as trademarks
or registered trademarks in one or more countries by their
respective owners. Rather than placing a trademark
symbol in every occurrence of a trademark name, Bosch
Security Systems, Inc. uses the names only in an editorial
fashion and to the benefit of the trademark owner with no
intention of infringing the trademark.
Hochiki is a trademark of Hochiki America Corporation.
Ordering Information
FLM‑325‑IM Contact Module
Allows compatible fire alarm control panels
(FACP) to supervise Form A or B dry contact
devices in a polling circuit
FLM-325-IM
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.asia
Represented by
© Bosch Security Systems 2011 | Data subject to change without notice
T7621673227 | Cur: en-US, V1, 25 May 2011