Bosch Appliances DS9400 Smoke Alarm User Manual


 
DS9400 Series | Release Notes for Firmware V2.07 | Trademarks
2 Bosch Security Systems | 8/06 | 36925V
Trademarks
Gentex™ is a trademark of Gentex Corporation, Fire
Protection Group
CleanMe® is a registered trademark of GE
Interlogix
1.0 Fixed Items in Firmware
Version V2.07
The D9400 Series Fire Alarm Control Panel (FACP)
V2.07 fixes two bugs:
When the Drill button was pressed, only the
Local Notification Appliance Circuits would
activate. This has been corrected, and the
DS9484 Remote NAC supply also activates.
In Firmware Version V2.06, a bug was created
when silencing a multiple output module
(DS9488/B or DS9489/B), causing some outputs
not to silence. This worked correctly in other
firmware versions, but worked incorrectly when
changing the silence priority feature.
2.0 Fixed Items in Firmware
Version 2.06
Version 2.06 firmware for the DS9400 Series Fire
alarm Control Panels (FACP) incorporates a change
to Preassigned Zone 61 and a bug fix for Outputs
assigned to Silencable points.
Preassigned Zone 61 – General Water flow
(Silencable) has been changed to a Non-
Silencable Zone type.
Preassigned Zone 53 – General Fire alarm
(Silencable) has been fixed so that a Non-
Silencable point will take priority over a
Silencable point.
1. This condition may happen when both
Silencable and Non-Silencable points are
mapped to the same output.
2. Version 2.05 and prior would configure the
output to Silencable or Non-Silencable
depending on the last event type activated.
Upgrade Information
If this firmware is installed in a control
panel that has been running version 1.x
software, it is necessary to erase the old
programming in the control panel and re-
select the control panel type when the
control panel is first powered up. Be
careful to select “1-DS9400”- an incorrect
selection cannot be undone.
3.0 Fixed Items in Firmware
Version 2.05
Version 2.05 firmware for the DS9400 Series Fire
Alarm Control Panels (FACP) incorporates a bug fix
for auto-programming and updates the panel to
work with the DS9431 with V1.04 ROM or later.
Auto-programming.
1. When selecting a device type of I/O, the
first address programs correctly but if any
device option is selected other than “no
device,” the second address results in an
“Address Error 2.” This V2.05 ROM fixes
this issue.
2. The Auto-program feature of the DS9400
with V2.04 ROM does not work properly if
a DS9431 V1.04 MUX driver or later is
installed. The DS9400 with V2.05 ROM is
backwards compatible with V1.04 and
earlier versions of the DS9431.
4.0 Fixed Items in Firmware
Version 2.04
Version 2.04 firmware for the DS9400 Series Fire
Alarm Control Panels (FACP) incorporates several
new features and improvements:
Gentex™ Sync Protocol. The control panel can
now send Gentex protocol to Gentex
Notification Appliance Circuit (NAC) devices.
Gentex NAC devices can be added directly to
the NAC circuits without a sync module.
CleanMe®. The control panel recognizes the
Clean-Me signal from Detection System’s F220
Series Smoke Detectors. If the smoke detectors
get dirty, a signal is sent on the two-wire loop,
and the control panel will annunciates that there
is a dirty detector on the loop.