D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
.
Bosch Security Systems, Inc. | 8/06 | F01U011791B 11
4.4.1 Menu Item and Function
Program the first ten menu items as indicated in
Table 3. This programming is necessary for the
D1256RB to operate properly. The first four keys on
the D1256RB execute the first four menu items
enabled at the keypad address. Menu items five
through ten are optional features that can be
programmed into the D1256RB system. Refer to the
Fire System User’s Guide (P/N: F01U011793) for further
explanation of these optional programmable items.
Ensure that CF 128 through CF 131 are
programmed E (enabled) and not P
(passcode required).
Table 3: Function List Description
Menu Item Function Description
1 128
ALARM SILENCE?
2 129
TROUBLE SILENCE?
3 130
DETECTOR RESET?
4 131
ANNUNCIATOR RESET
5 9
VIEW MEMORY?
6 10
VIEW PT STATUS?
7 12
FIRE TEST?
8 21
VIEW LOG?
9 29
REMOTE PROGRAM?
10 32
DISPLAY REV?
4.4.2 CC Address #
CC = command center = keypad
Program the keypad (command center) addresses as
Yes for the first four menu items and for the optionally
programmed menu items five through ten.
4.4.3 Passcode Worksheet
Figure 17: Example – Fire Passcode Worksheet
User (Passcode) Worksheet (Users 000 to 029)
Area Authority
User
##
#
Passcode
User
Group
1 2 3 4 5 6 7 8
User Name
000
123 __ __ __ __ __ __
____
15 15 15 15 15 15 15 15
SERVICE
PASSCODE
001
1 2 5 6 0 0
____
14
__ __ __ __ __ __ __
USER 1
Refer to User (Passcode) Worksheet in the program record sheet for the control panel.
4.4.4 Passcode
A special passcode must be programmed as a valid passcode for the system to work properly. This passcode is
used in Custom Functions 128 through 131. Use any user number to establish this mandatory valid passcode. You
must also create it as a valid passcode in the area to which the D1256RB is assigned. Use Authority Level 14
together with the passcode you select. Ensure that Passcode Arm is disabled (blank) for the Authority Level.
Refer to Authority Level Selections in the program record sheet for the control panel.