Beckett CG10A Burner User Manual


 
General Burner Description:
Install __________ Beckett Model ________ Gas Burner forced draft flame retention power gas burners.
Burners shall be capable of burning ______BTUs (natural gas or propane) with a specific gravity of ____(0.64
or 1.56). Gas Pressure supplied to the burner gas train connection shall be a minimum of _____ inches W.C.
(PSIG) at full high rate and a maximum of _____ inches W.C. at static conditions.
Each burner shall be listed by Underwriters Laboratories and shall bear the appropriate UL label. In addition to
the UL requirements, all equipment and installation procedures will meet the requirements of CSD-1 (FM,
Swiss RE). Each burner shall be designed and constructed as an integrated combustion system package.
Burner Construction:
Burner housing shall be of cast aluminum construction. The burner mounting flange must support the burner
weight on the appliance independent of any support and shall be seal welded to the air tube. Burners shall be
furnished with a stainless steel flame retention head, capable of withstanding temperatures up to 1400 degrees
F. The combustion head assembly shall incorporate an air diffuser, gas spuds downstream of air diffuser and
direct ignition electrodes. The combustion gun assembly shall be removable and have the ability to be set or
replaced. Full access to the burner combustion gun assembly shall be available without removing the burner
chassis from the appliance. Air required for combustion shall be supplied by a blower, mounted integral to the
burner. The blower wheel shall be of a forward curved “squirrel Cage” design and shall be directly driven by a
1/3HP, 3450rpm, _____volt, 60Hertz, ____Phase motor. The burner shall be equipped with an SPDT
differential air pressure switch interlocked and continuously monitored to prevent burner operation if there is
insufficient combustion air.
Ignition:
The burner ignition system shall directly ignite the natural gas or propane fuel. The ignition spark shall be
generated by a 6000 volt electronic igniter, and directed by porcelain insulated electrodes located on the
combustion head assembly. Ignition shall occur only at a reduced firing rate, and only after the flame is proven
shall full rate be actuated.
Burner Control Panel:
All control components shall be mounted and wired in a remote 12 x 16 panel. The panel shall incorporate an
Easy Access cover and Power On and Fuel On indicating lights. All wiring for remote panel electrical
components shall be factory pre-wired to a terminal strip within the control panel. A junction box pre-wired to
the burner components shall be mounted on the burner. It shall have a terminal strip, which will match a
terminal strip in the remote panel. Field wiring will be required between the burner mounted junction box and
the remote control panel.
Gas Train:
The gas train shall consist of a manual shutoff cock, redundant gas valve and regulating gas valve. The gas
train shall meet UL and CSD-1 requirements and include a manual reset low gas pressure switch and manual
reset high gas pressure switch.