Bard W24A to W70A Air Conditioner User Manual


 
Form No. S3408-1011
Supersedes S3408-710
Page 3 of 8
Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.
Standard on all units is the barometric fresh air damper. All packages can be ordered built-in at the factory or can be easily field-installed
at the time of installation of the Wall-Mount, or can be retrofitted at a later date.
COMMERCIAL ROOM VENTILATOR
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the
service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be
introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens
during blower operation and closes when the blower is off. Adjustable blade stops allow different
amounts of outside air to be introduced into the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which
restricts any outside air from entering the unit. The blank off plate should be utilized in applications
where outside air is not required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside
ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet
openings and to be mixed with the conditioned air. The two position damper can be fully open or
closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The
damper can be controlled by indoor blower operation or can be field connected to be managed based
on building occupancy.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows
outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air
inlet openings. It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air
quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily
adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by
indoor blower operation or field controlled based on room occupancy. The CRV is power open - spring
return on power loss. Complies with ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air
Quality.”
ECONOMIZER - EIFM OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system
controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer
is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling
requirements without running the compressor. This in turn provides lower operating costs, while extending
the life of the compressor.
Standard Features:
One Piece Construction - Easy to install with no mechanical linkage adjustment required.
Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to prevent
pressurization of tight buildings.
Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.
Proportioning Type Control - for maximum “free cooling” economy and comfort.
Moisture Eliminator & Prefilter - permanent, washable aluminum construction.
Enthalpy Control - adjustable to monitor outdoor temperature and humidity.
Minimum Position Potentiometer - adjustable to control minimum damper blade position for ventilation
purposes.
Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require
separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing
dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
BAROMETRIC FRESH AIR DAMPER
MOTORIZED FRESH AIR DAMPER
ECONOMIZER