Avalon Stoves 790 Stove User Manual


 
Stove Installation (for qualified installers only) 13
Travis Industries 93508133 4020509
Mobile Home Requirements
Outside air must be installed - see "Outside Air Requirements" on page 11
Chimney connector and chimney must be one of the following types:
DURAVENT model DVL with DURATEC chimney
DURAVENT model DVL with DURA-PLUS chimney
AMERI-TEC model DCC with model HS chimney
SECURITY model DL with SECURITY model ASHT or S2100 chimney
METAL-FAB model DW with TG chimney
GSW Double Wall Chimney Connector with Super Chimney Twenty-One
SELKIRK METALBESTOS model DS connector with model SSII chimney
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar order an appliance
adapter for the connector being used.
Stove placement must maintain the following clearances to combustibles (drywall, furniture, etc.)
Minimum Clearance
(See the illustration below)
745
Reduced
Clearance
Connector
790
Reduced
Clearance
Connector
A Sidewall to stove 11" 11"
B Backwall to stove 13" 8 1/2"
C Cornerwall to stove 7 1/2" 7 1/2"
D Connector to sidewall 19 1/2" 19 1/2"
E Connector to backwall 9"* 8 3/4"
F Connector to cornerwall 11"* 15"
* These are minimum clearances, not installation dimensions. Connector position will vary
depending upon brand. First establish the stove clearances, install the 45° connector to the stove, then
determine the position of the connector.
Straight Installations
a
b
d
e
Corner Installations
c
f
NOTE:
Measure clearances to the stove top.
If using offsets, use the connector clearance listed to the
right, not the connector manufacturer's
clearance.
The appliance must be secured to the floor (consult your
building official). Secure the outside air boot to the floor
and stove to insure the stove does not dislocate.
Mobile home installations require a spark arrester at the
chimney termination.
The appliance must be grounded to the chassis of the
mobile home (consult your building official).
WARNING: DO NOT INSTALL IN SLEEPING ROOM.
CAUTION: THE STRUCTURAL INTEGRITY OF THE
MOBILE HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
Minimum Stove
Clearance
(as outlined above)
12-1/4
Min.
Minimum Connector
Clearance
(as outlined above)