Atlas MLGC180W Indoor Furnishings User Manual


 
4
598-1098-02
Motion
Motion
Maximum Range Maximum
Coverage Angle
RANGE
10 5 1 TEST
ON-TIME
70 ft.
(21 m)
8 ft.
(2.4 m)
180°
MIN MAX
Least Sensitive Most Sensitive
Sensor
NOTE:
If fixture is mounted higher than 8 ft. (2.4 m), aiming
the sensor down will reduce coverage distance.
The detector is less sensitive to motion directly towards it.
Loosen the clamp screw in the
sensor ball joint and gently
rotate the sensor.
Walk through the coverage
area noting where you are
when the lights turn on (also,
the LED will flash several times
when motion is detected). Move
the sensor head up, down, or
sideways to change the cover-
age area. Keep the sensor at
least 1" (25 mm) away from
the bulbs.
Adjust the RANGE as needed.
RANGE set too high may
increase false triggering.
Secure the sensor head by
tightening the clamp screw.
Do not overtighten the screw.
Set the amount of TIME you want the lights to stay
on after motion is detected (1, 5, or 10 minutes).
Bottom of Sensor
Avoid aiming the control at:
• Objects that change temperature rapidly, such as
heating vents and air conditioners. These heat
sources could cause false triggering.
• Areas where pets or traffic may trigger the control.
Nearby large, light-colored objects reflecting light
may trigger the shut-off feature. Do not point other
lights at the sensor.
Clamp
Screw
Ball
Joint
Aim Sensor
Down for Short
Coverage
Aim Sensor
Higher for Long
Coverage
WARNING: Risk of fire. Do not aim the bulbs
at a combustible surface within 3 ft. (1 m).
TEST AND ADJUSTMENT
Turn on the circuit breaker and light switch.
NOTE: Sensor has a 1
1
/
2
minute warm up period
before it will detect motion. When first turned
on, wait 1
1
/
2
minutes.
NOTE: Meets the ENERGY STAR
®
guidelines when
used with 120 W Max bulbs.
Turn the RANGE control to the medium position
(halfway between MIN and MAX) and the ON-TIME
control to the TEST position.