Ariston 47-116-10 Boiler User Manual


 
20
B023
The boiler is designed to make it easy to analyse the combustion by-products.
Using the especially designed apertures, readings can be taken on the
temperature of the combustion by-products and of the combustion air, as well
as of the concentrations of O
2
and CO
2
, etc.
The best maximum-power test conditions for the heating system are when the
selector “C” is turned to the flue analysis setting.
The discharge/ventilation of the exhaust fumes can be monitored to check for
losses in general pressure in the system. This is done to eliminate the cause of
lighting failure with the main burner not indicated by a shutdown status.
With a differential manometer connected to the test socket on the combustion
chamber, the DP value for the air pressure switch can be taken. The measured
value should not be less than 10 mbar under maximum thermal power
conditions (with the knob “C” on the flue test setting) in order for the unit to
function properly and without interruption.
- the potentiometer for the maximum thermal power for the heating system,
maximum thermal power setting (factory set at the maximum value, unless
indicated otherwise on the adhesive sticker located in proximity to the
potentiometer);
- The connection for the diagnostic device (TCS-TCS2).
G20 5.5 mm c.a.
G25 4.5 mm c.a.
G30-31 1.8 mm c.a.
The boiler is equipped with the following safety systems (see section 3.3 for
references):
1 - Ignition Failure
This control signals an ignition failure on the burner 7 seconds after a lighting
failure. The L.E.D. “B”.will turn on to signal the shutdown status.
The system can be reset by pressing and releasing the button “A” after
checking to make sure that the gas valve is open. Repeat this process until the
burner lights.
2 - Circulation Failure
This control signals that the safety pressure switch on the primary circuit has
not sensed a pressure of at least 1 bar within 40 seconds of the activation of
the circulation pump, it shuts off the boiler and lights the L.E.D. “D”. The system
can be reset (after the pressure has been brought up to the proper level) by
using the On/Off switch “L”.
3 - Overheating
This control shuts off the boiler in the case where the primary circuit reaches a
temperature in excess of 110°C. The L.E.D. “G” will come on to signal this shut
3.6 Combustion Analysis
3.7 Fume Discharge
Monitoring
3.8 Boiler Safety Systems