AquaStar 125B NG Water Heater User Manual


 
7
The flue connection for the AquaStar 125B is 5 inches.
However, in Canada, for installations at high altitude (2000-
4500 feet above sea level) a six inch flue is required. A 5"
by 6" flue adaptor must be affixed to the flue collar of the
AquaStar with at least two screws. See figure 3
Fig. 3 - Flue Adaptor for High Altitude Installations
WARNING: Failure TO INCREASE THE VENT SIZE TO
SIX INCHES AND/or assure that the manifold pressure is
set to proper value listed for applications at high altitudes
will cause unsafe venting, asphyxiation, and will void IAS
Certification.
GAS CONNECTIONS and Gas Regulator
Before connecting the gas supply, check the rating plate
on the right side of the front cover to be sure that the heater
is rated for the same gas to which it will be connected.
In the United States: The installation must conform with
local codes or, in the absence of local codes, the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
In Canada: The Installation should conform with CGA B149
INSTALLATION CODES and /or local installation codes.
NOTE: The Aquastar 125 B is supplied with a gas
pressure regulator that must be installed on the heater
before attaching the gas supply line. See figure 4.
Failure to install the gas regulator as shown in figure
4 will be a violation of IAS certification of the unit.
The regulator supplied with the heater is preset for
the gas shown on the rating plate to the correct
pressure. It is an appliance level regulator designed
for (low inlet) pressure (less than 1/2 Psig or 15” W.C.)
DO NOT connect to an unregulated or high pressure
propane line or to a high pressure commercial natural
gas line.
GAS LINE SIZE
It is strongly recommended that the natural gas pipe line
be 3/4" for the entire distance. If the maximum length is
above 40 feet, use 1" line. Flexible tubing is NOT
recommended, but if it is to be used, oversize it. With LP
gas installation, the recommended sizes are 5/8" up to a
maximum of 20 feet distance, 3/4" up to 50 ft distance
and 7/8" up to 100 feet.
National Fuel Gas Code requires that a sediment trap (drip
leg) be installed on gas appliances not so equipped. The
drip leg must be accessible and not subject to freezing
conditions. Install in accordance with the recommendations
of the serving gas supplier.
WARNING: The heater must be disconnected from the
gas supply piping system during any pressure testing of
that system at test pressures in excess of 0.5 psig.
The water heater must be isolated from the gas supply
piping system by closing the manual shutoff valve during
any pressure testing of the gas supply piping system at
test pressures equal to or less than 0.5 psig.
The water heater, including the pressure regulator provided
with it, must not be operated at gas supply pressures in
excess of 0.5 psig. If overpressure has occurred, such as
through improper testing of the gas lines or emergency
malfunction of the supply system, the gas valve and
regulator must be checked for safe operation. Make sure
that the regulator vent is protected against blockage. Vent
blockage could occur during ice storms.
When your connections are made, check for gas leaks at
all joints (not just the ones you made). Apply some soapy
water to all gas fittings and gas valve. Soap bubbles are
a sign of a leak.
NOTE: Do not apply soap solution to pilot filter screen or
pilot orifice area. If you have a leak, shut off the gas. After
verifying that required gaskets are in place, tighten
appropriate fittings to stop leak. Turn the gas on and check
again with a soapy solution. Never test for gas leaks
using a match or flame.
Fig. 4 - Installation of Gas Pressure Regulator
(660 meters) above sea level. On appliances being
installed above 2000 ft (660 meters) elevation, the inlet
gas pressure should be set at installation to the value
shown below.
NOTE: The gas pressures specified below refer to
pressures taken at the test pressure nipple on the gas
inlet pipe just above the regulator (See Fig 4). These
readings should be taken while the heater is operating
at full input — i.e. maximum water flow with the
temperature dial selector turned all the way clockwise.
MAXIMUM INLET GAS FLOW PRESSURE SETTING
5” X 6” ADAPTOR
USED ON HIGH ALTITUDE
Altitude Natural Gas Liquid Propane
inches W.C: inches W.C:
0' - 2.000 ft 5.7" 10.5"
2.000 ft - 4.500 ft 4.6" 8.4"
GAS INLET PIPE
PRESSURE TAP
PRESSURE REGULATOR
The pressure regulator provided with the heater is adjusted
to deliver the proper gas pressure (as indicated on the
rating plate and in the manual for altitude up to 2000 feet
Above 4.500 ft consult your local gas supplier.