Aprilaire 1510 Air Cleaner User Manual


 
Model 1510 Media Air Cleaner
Installation Instructions
1. High voltage may cause serious
injury from electrical shock.
Disconnect power to the
furnace/air handler before
starting installation.
2. Sharp edges may cause injury
from cuts. Use care when cutting
and handling sheet metal.
WARNING
1. To prevent component failure, do not install the air cleaner on the warm
air supply or in an area where the temperature may exceed 140°F. This
may include areas above heat exchangers in downflow furnaces or above
exhaust flues in lowboy furnace cold air returns.
2. Installation must be done by a qualified heating and air conditioning
professional. Read instructions thoroughly before beginning installation.
3. Do not install air cleaner downstream of a UV light. UV lamps will cause
degradation of the filtering media.
CAUTION
SPECIFICATIONS
DIMENSIONS
TABLE 1 – Dimensions (inches)
Model A B C D E F G H
1510
28-3/4 28-1/16 23-7/8 6-3/4 30-1/16 23-7/8 28-3/4 31
A
B
without door
C
D
E
with door
F
G H
90-1333
Model 1510
Airflow Capacity
up to 3000 CFM maximum
Replacement Media
Model 510 or 513 with SelfSeal
Max. Equipment Weight
Cabinet will support 400 lb. static load
Air Cleaner Operating Environment
Temperature:F
140°F. Humidity: 0
90% non-condensing.