APC ACPSC3500 Air Conditioner User Manual


 
9InRoom SC 60 Hz User Manual
Installation
Location
Requirements
When deciding where to locate the cooling
unit, consider cooling needs, air flow, and
the location of the electrical outlet. The
cooling unit can be no more than 2.4 m
(8 ft) from the electrical outlet, condenser
intake and exhaust access.
Cooling needs. Position the cooling unit
as close as possible to the main heat source
that requires cooling.
Air flow. Position the rear of the cooling
unit at least 500 mm (20 in) away from a
wall or other equipment.
Location of electrical outlet. Place the
cooling unit no farther than 2.4 m (8 ft)
from a dedicated 120V, 60Hz, 15A branch
circuit receptacle.
Electrical Hazard: Do not use extension cords with this equipment. Using an extension
cord reduces circuit protection and will void the warranty.
Caution: To help avoid loss of cooling, only connect this equipment to a single-outlet
dedicated circuit.
O
N
/OF
F
MODE
S
L
E
E
P
F
A
N
T
E
M
P
T
I
ME
I
n
Ro
o
m
S
C
> 500 (20)
> 500 (20)
na3362a
Dimensions are shown in mm (in).