A.O. Smith BTN 120 THRU 400/A Series Water Heater User Manual


 
9
TYPE B GAS VENT
Multiple Gas Fired Tank-Type Heaters
When venting multiple tank type heaters using Type B
vent pipe, follow the installation diagram (figure 4) and
tables below which give sizing and data based upon
NFPA 54/ANSI Z223. 1992.
TABLE 6. TECHNICAL DATA VENTING
MODEL BTN-120
Input: 120,000 Btu/hr Total Vent Height (Feet)
Vent Connector Size: 5 inches 6 8 10 15 20 30 50 100
Input Btu/hr Rise Vent Connector Diameter (Inches)
120,000 1 Ft. 6 6 5 5 5 5 5 5
120,000 2 Ft. 5 5 5 5 5 5 5 5
120,000 3 Ft. 5 5 5 5 5 5 5 5
Number of Combined Input
BTN 120 Heaters in Thousands of Btu/hr Manifold and Common Vent Diameter (Inches)
2 240,000 7 7 6 6 6 6 6 6
3 360,000 8 8 7 7 7 6 6 6
4 480,000 9 9 9 8 8 7 7 6
MODEL BTN-154
Input: 154,000 Btu/hr Total Vent Height (Feet)
Vent Connector Size: 6 inches 6 8 10 15 20 30 50 100
Input Btu/hr Rise Vent Connector Diameter (Inches)
154,000 1 Ft. 6 6 6 6 6 6 6 6
154,000 2 Ft. 6 6 6 6 6 6 6 6
154,000 3 Ft. 6 6 6 6 6 6 6 6
Number of Combined Input
BTN 154 Heaters in Thousands of Btu/hr Manifold and Common Vent Diameter (Inches)
2 308,000 7 7 6 6 6 6 6 6
3 462,000 8 8 7 7 7 6 6 6
4 616,000 9 9 9 8 8 7 7 6
MODEL BTN-180,199, 200
Input: 180,000, 190,000 and 199,000 Btu/hr Total Vent Height (Feet)
Vent Connector Size: 6 inches 6 8 10 15 20 30 50 100
Input Btuh/hr Rise Vent Connector Diameter (Inches)
180,000 1 Ft. 7 7 6 6 6 6 6 6
190,000 1 Ft. 7 7 7 6 6 6 6 6
199,000 1 Ft. 7 7 7 6 6 6 6 6
180,000 2 Ft. 6 6 6 6 6 6 6 6
190,000 2 Ft. 7 6 6 6 6 6 6 6
199,000 2 Ft. 7 7 6 6 6 6 6 6
180,000 3 Ft. 6 6 6 6 6 6 6 6
190,000 3 Ft. 6 6 6 6 6 6 6 6
199,000 3 Ft. 6 6 6 6 6 6 6 6
Number of Combined Input
BTN Heaters in Thousands of Btu/hr Manifold & Common Vent Diameter (Inches)
360,000 7 7 6 6 6 6 6 6
2 380,000 7 7 7 6 6 6 6 6
398,000 6 7 7 6 6 6 6 6
540,000 7 6 6 6 6 6 6 6
3 570,000 7 6 6 6 6 6 6 6
597,000 6 7 6 6 6 6 6 6
720,000 6 6 6 6 6 6 6 6
4 760,000 6 6 6 6 6 6 6 6
796,000 6 6 6 6 6 6 6 6