A.O. Smith AOSRG45700 Water Heater User Manual


 
www.hotwater.com
For Technical Information and Automated Fax Service, call 800-527-1953. A.O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
MODEL
NUMBER
FIRST
HOUR
RATING
GALLONS
ENERGY
FACTOR
GAL.
CAP.
BTU
INPUT
PER HOUR
RECOVERY
90ºF RISE
GALLONS
PER HOUR
A B C D E F
VENT
OUTLET*
APPROX.
SHIPPING
WEIGHT
(LBS)
GDV-40 73 .62 40 38,000 41 68 54-3/4 22-1/4 16 12-1/4 45-1/4 Co-Axial 167
GDV-50 87 .60 50 42,000 45 76 63-3/4 22-1/4 16 12-1/4 54 Co-Axial 185
GDVT-50 88 .59 50 50,000 55 76 64-3/4 22-1/4 16-1/4 12-1/2 55-1/2 Co-Axial 187
GDV-75 131 .59 75 55,000 60 76 65-3/4 26-1/4 16-1/4 12-1/2 55-1/2 Co-Axial 310
Recovery capacities based on actual performance tests.
* Dual-channel system has 3˝ vent pipe inside 6˝ air intake pipe, for the 40 & 50 gallon models.
The 75 gallon model uses a 4” x 7” co-axial pipe.
All Models Have 2” Foam Cavity.
Water connection 3/4” male all models.
75 gallon water connections are 12” on center.
DIMENSIONS IN INCHES
E
F
B
A
D
FRONT
MAX VENT
80
C
EXTERIOR
WALL
6 DIA.
MIN VENT
17
42°
47°
25-1/4
TOP
DRAIN
T&P
Important! Vent Installation and Termination Requirements
n Maximum horizontal vent distance is 80” to outside of exterior wall.
n Minimum horizontal vent distance is 17” to outside of exterior wall.
n Vent pipes may be trimmed (cut) for short vent installations.
n For vent installation less than 30” the vent restrictor is required.
Place restrictor over the flue outlet on heater before installing the outlet vent
pipe to the heater.
n Recommended installation height for the heater vent pipe should be
68” for 40 gallon models and 76” for the 50-gallon and 75-gallon
models (vent height).
n Offset Vent Arrangement
1. When replacing an existing direct vent model,
the new vent pipe may drop from the minimum
vent height as much as 7 1/4” to exit through the
existing vent opening in the exterior wall.
2. Vent may have one horizontal 90 degree turn before
exiting through exterior wall (Do not combine both
offset vent arrangements in one installation) (See
examples in the installation manual)
n High Rise Vent Arrangement
3. When vent termination is more than 80” above the
base of the heater. The horizontal vent run must be
a minimum of 22” from the center of the heater to
the outside exterior wall surface. (See example in the
installation manual)
n Vent termination clearance hole through the exterior
wall should be approximately 7” diameter.
n Snow accumulation and drifting should be considered
when locating the termination.
n An optional wire grill vent cap protector is available
through the parts department. Part number 9006627.
n See the installation manual for complete installation
and venting requirements.
Residential Gas Water Heaters
DIRECT-VENT
AOSRG45700
Page 2 of 2
Revised April 2008
40 & 50 gal.
25-1/4
75 gal.
29-1/2
6” DIA. on 40 & 50 Gal. Models
7” DIA. on 75 Gal. Models
75 gal. vent
termination
cap is not
interchangeable
with vent cap
on 40 & 50 gal.
models