A.O. Smith 185874-001 Water Heater User Manual


 
11
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certied by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment of
materials as meeting the requirements for Relief Valves for Hot Water
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements
of ASME.
If replaced, the valve must meet the requirements of local codes, but
not less than a combination temperature and pressure relief valve
certied as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water heater
(150 psi = 1,035 kPa) and a discharge capacity not less than the water
heater input rate as shown on the model rating plate.
For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly into
the tting of the water heater designed for the relief valve. Position
the valve downward and provide tubing so that any discharge will exit
only at any distance below the structural oor. Be certain that no
contact is made with any live electrical part. The discharge opening
must not be blocked or reduced in size under any circumstances.
Excessive length, over 30 feet (9.14 m), or use of more than four
elbows can cause restriction and reduce the discharge capacity of
the valve, see Figure 7.
No valve or other obstruction is to be placed between the relief valve
and the tank. Do not connect tubing directly to discharge drain unless
a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or
property damage, the relief valve must be allowed to discharge water
in quantities should circumstances demand. If the discharge pipe is
not connected to a drain or other suitable means, the water ow may
cause property damage.
The Discharge Pipe:
Shall not be smaller in size than the outlet pipe size of the valve, or
have any reducing couplings or other restrictions.
Shall not be plugged or blocked.
Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both the
temperature-pressure relief valve, and the discharge pipe.
Shall terminate at an adequate drain.
Shall not have any valve between the relief valve and tank.
The temperature-pressure relief valve must be manually operated at
least once a year. Caution should be taken to ensure that (1) no one
is in front of or around the outlet of the temperature-pressure relief
valve discharge line, and (2) the water manually discharged will not
cause any bodily injury or property damage because the water may
be extremely hot.
If after manually operating the valve, it fails to completely reset and
continues to release water, immediately close the cold water inlet
to the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.
FIGURE 7.
FILLING THE WATER HEATER
Never use this water heater unless it is completely full of water. To
prevent damage to the tank, the tank must be lled with water. Water
must ow from the hot water faucet before turning “ON” gas to the
water heater.