American Water Heater AHCG/HCG3 60T 120 - AHCG3/HCG3 100T 250 Water Heater User Manual


 
67
DIAGRAMS
CCB - CENTRAL CONTROL BOARD LAYOUT
1 Retry
Use Yes
Type Tstat
Spare
Ext
Input
3
Retries
No
Vent
Spare
OPEN
1 2 3 4
3
2
1
6
5
4
9
8
7
12
11
10
15
14
13
J6
J7
3 24 1
1
2
J15
84
5
6
7
1
2
3
J13
3
4
1
2
J10
1
3
5
2
4
J1
1
3
4
2
J2
1
4
2
1
2
J3
J5
J4
S1 DIPSWITCH
J16
J9
J11
S1 DIPSWITCH DETAIL
CCB (CENTRAL CONTROL BOARD)
1 Retry
Use Yes
Type Tstat
Spare
Ext
Input
3
Retries
No
Vent
Spare
OPEN
1 2 3 4
Dipswitch Operation:
Along one side of the dipswitch array there are numbers, 1-4. On the other side of the dipswitch
is the word “OPEN.” The dipswitches are rocker type switches, if one side of the rocker is down the
other side will be up. Pressing a rocker down on the side of the array labeled “OPEN,” opens the switch.
Pressing a rocker down on the side of the array labeled with the numbers 1-4 closes the dipswitch.
CHANGING NUMBER OF IGNITION TRIALS BEFORE LOCK OUT
NOTE: Always turn off power to the water heater before changing dipswitch settings.
Set dipswitch #4 to the open position for 1 trial for ignition before Ignition Failure lock out. Set dipswitch
#4 to the closed position for 3 trials for ignition before Ignition Failure lock out.
Figure 65