26 APC NetworkAIR AFX Series: Electrical Data
Electric Reheat1828 ton
HUMIDIFIER Electric Steam or None
VOLTAGE 208 230 460 575 208 230 460 575
18T FLA Air 85.7 82.5 41.1 32.9 74.5 76.1 37.9 31.5
Water 79.3 76.1 37.9 30.3 71.3 72.9 36.3 30.2
Glycol 89.9 86.7 44.1 34.5 76.6 78.2 39.4 32.3
Remote Condensing 65.2 65.2 32.6 27.4 48.8 50.4 25.2 21.4
WSA Air 113.7 110.1 56.2 44.3 98.6 101.0 51.1 42.0
Water 113.7 110.1 56.2 44.3 98.6 101.0 51.1 42.0
Glycol 113.7 110.1 56.2 44.3 98.6 101.0 51.1 42.0
Remote Condensing 81.5 81.5 40.8 34.3 61.5 63.0 31.5 26.8
MOP Air 125.0 125.0 70.0 50.0 125.0 125.0 60.0 50.0
Water 125.0 125.0 70.0 50.0 125.0 125.0 60.0 50.0
Glycol 125.0 125.0 70.0 50.0 125.0 125.0 60.0 50.0
Remote Condensing 70.0 70.0 35.0 30.0 50.0 60.0 30.0 25.0
20T FLA Air 104.8 105.0 52.2 43.5 102.6 105 52.2 43.5
Water 98.6 101.0 50.2 41.9 98.6 101.0 50.2 41.9
Glycol 110.0 107.6 53.5 44.5 105.2 107.6 53.5 44.5
Remote Condensing 92.2 92.6 46.3 39.0 73.2 75.6 37.8 32.1
WSA Air 144.7 141.0 68.3 55.0 137.4 141.0 68.3 55.0
Water 144.7 141.0 68.3 55.0 137.4 141.0 68.3 55.0
Glycol 144.7 141.0 68.3 55.0 137.4 141.0 68.3 55.0
Remote Condensing 115.3 115.8 57.9 48.8 91.5 94.5 47.3 40.1
MOP Air 175.0 175.0 80.0 60.0 150.0 150.0 80.0 60.0
Water 175.0 175.0 80.0 60.0 150.0 150.0 80.0 60.0
Glycol 175.0 175.0 80.0 60.0 150.0 150.0 80.0 60.0
Remote Condensing 100.0 100.0 50.0 40.0 80.0 80.0 40.0 35.0
26T FLA Air 118.9 108.6 54.2 45.1 109.7 108.6 54.2 45.1
Water 110.5 104.8 52.3 43.6 105.5 104.8 52.3 43.6
Glycol 122.4 110.6 55.2 45.7 111.5 110.2 55.0 45.7
Remote Condensing 92.2 92.6 46.3 39.0 73.2 75.6 37.8 32.1
WSA Air 156.1 151.2 68.8 57.5 143.8 147.4 68.8 57.5
Water 156.1 151.2 68.8 57.5 143.8 147.4 68.8 57.5
Glycol 156.1 151.2 68.8 57.5 143.8 147.4 68.8 57.5
Remote Condensing 115.3 115.8 57.9 48.8 91.5 94.5 47.3 40.1
MOP Air 175.0 175.0 80.0 60.0 175.0 175.0 80.0 60.0
Water 175.0 175.0 80.0 60.0 175.0 175.0 80.0 60.0
Glycol 175.0 175.0 80.0 60.0 175.0 175.0 80.0 60.0
Remote Condensing 100.0 100.0 50.0 40.0 80.0 80.0 40.0 35.0
28T FLA Air 115.2 107.1 53.5 44.7 108.1 107.1 53.5 44.7
Water 107.7 103.7 51.8 43.3 104.3 103.7 51.8 43.3
Glycol 117.9 108.3 54.1 45.1 109.4 108.3 54.1 45.1
Remote Condensing 92.2 92.6 46.3 39.0 73.2 75.6 37.8 32.1
WSA Air 156.1 151.2 78.9 63.0 143.8 147.4 75.5 62.6
Water 156.1 151.2 78.9 63.0 143.8 147.4 75.5 62.6
Glycol 156.1 151.2 78.9 63.0 143.8 147.4 75.5 62.6
Remote Condensing 115.3 115.8 57.9 48.8 91.5 94.5 47.3 40.1
MOP Air 175.0 175.0 100.0 80.0 175.0 175.0 90.0 70.0
Water 175.0 175.0 100.0 80.0 175.0 175.0 90.0 70.0
Glycol 175.0 175.0 100.0 80.0 175.0 175.0 90.0 70.0
Remote Condensing 100.0 100.0 50.0 40.0 80.0 80.0 40.0 35.0
FLA= Full Load Amperes MOP=Maximum Overcurrent Protection WSA=Wire Size Amperes
*Values are calculated based on 3 phase power