Amana *D(H Furnace User Manual


 
42
GME8
B
LOWER
P
ERFORMANCE
D
ATA
Tons AC
at 0.5" 0.6 0.7 0.8
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
T1 - YELLOW 1.5 875 ---- 793 ---- 736 ---- 674 ---- 592 ---- 556 509 460
T2 - RED 2.0 1032 43 965 46 914 49 861 ---- 810 ---- 756 712 659
T3 - ORANGE 2.5 121737115339109840105142100944 964918877
T4 - BLUE 3.0 136533131334126835122136117238112910861054
T5 - BLACK 3.5 154929150530146030142031137832135013051268
T1 - YELLOW 2.5 126847119849115151109254104157 988932883
T2 - RED 3.0 136244130545126147121249117051112110741021
T3 - ORANGE 3.5 157638151939147340142642139842134112901252
T4 - BLUE 4.0 1755----171135165736162736157938154815021463
T5 - BLACK 5.0 2183 ---- 2128 ---- 2094 ---- 2060 ---- 2014 ---- 1992 1944 1847
T1 - YELLOW 3.0 146651141552135755130657124859120211441088
T2 - RED 3.5 164245159646155248149949144951138813521306
T3 - ORANGE 4.0 175042175042170743166744161046157415311486
T4 - BLUE 4.0 187040180541178242173743170144165616061571
T5 - BLACK 5.0 2297 ---- 2297 ---- 2224 ---- 2106 35 2014 37 1896 1813 1669
Notes:
(CFM & Temperature Rise vs. External Static Pressure)
0.1 0.2 0.3 0.4 0.5
Model
Heating Speed
As Shipped
Motor Speed
EXTERNAL STATIC PRESSURE (Inches Water Column)
GME81005C***
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two
return filters, this chart assumes both filters are installed.
• All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling and heating speed as needed.
GME80603B***
GME80805C***
• For most jobs, about 375 - 400 CFM per ton when cooling is desirable.
• Temperature rise data is based on 2nd-stage heat. First-stage heat is 75% of rise indicated above.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• This chart is for information only. For satisfactory operation, external static pressure
should
not exceed value shown on the rating plate.
• The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same
temperature rise at a particular CFM, while ESP at the CFM will be lower.
• Factory Motor Speed Setting: T1 = 1st Stage Ht, T2 = 2nd Stage Ht, T5 = Cooling.