Aico Ei166RC Smoke Alarm User Manual


 
for dwellings where occupants may be at high risk (e.g. elderly)
OPTIMUM PROTECTION
LD1
Optimum Protection LD1: As LD2, but in addition
Smoke or Heat Alarms should be located in all rooms
and other areas of the dwelling.
(apart from toilets or bathroom)
Multi Storey Dwelling LD1
Heat Alarms located in:
(Heat Alarms must be within 5.3m of potential fire
sources)
each Kitchen
garages
Living
Room
Bedroom Bathroom
Kitchen
Bedroom
Shower
Garage
Smoke or Heat Alarms located in:
each Living room (i.e. most frequently used
daytime room)
Smoke Alarms located:
on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
in all other rooms & areas other than listed below
(apart from toilets & bathrooms )
Bedroom
Bedroom Bedroom
Kitchen / Dining Room
Living Room
Bathroom
Single Storey Dwelling LD1
Heat Alarm
do not fit alarm
Ionisation or Optical
Smoke Alarm
Optical Smoke Alarm
7
B16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 6