Aarrow Fires TF 70 Stove User Manual


 
WATER CONNECTIONS
Heating systems
The size of the heating system which can be run,
will depend on the output rating of the appliance.
It will be necessary to work out heat loss
calculations for the system proposed in order to
establish the kW/hr rating. An appliance that will
meet this figure can then be chosen; (for boiler
outputs please refer to the brochure).
The constructional requirements of installing and
connecting the appliance also need to be taken into
account when selecting. Design and calculations
for individual heating systems should be carried out
by a qualified heating engineer. In many cases your
supplier will be able to offer advice and assistance.
Direct Systems
Stainless steel boilers, either factory fitted or
retro-fitted as add-in boilers enable connection to
direct systems to be made without the need to
change the cylinder or to fit an expansion tank.
This applies to domestic water supply only and
should not be done when in an area with soft
water.
If radiators are used then an indirect system must be
utilised.
To connect the cylinder use 28mm copper pipes.
Ensure that the pipes rise continuously to the
cylinder.
Ensure that the runs are not too long, i.e. 20ft
maximum each for flow and return. Install the
cylinder above the level of the fire, and as close to
it as possible. (the higher the cylinder the faster the
circulation). Ensure that no valves are present in the
circulating pipes.
Indirect Systems - The Domestic Hot Water
Circuit
In addition to providing hot water the primary
circuit is essential in providing a "heat leak" to
absorb excessive heat produced in the event of the
circulation pump shutting down.
Heat is produced in varying quantities while the
fire is alight and care must be taken to ensure that
effective circulation can occur around the primary
circuit to carry heat away and thus stop boiling.
The output of any radiator installed as a "heat leak"
should not be less than 10% of the rated output of
the appliance. The radiator should not
be fitted
with a control valve.
The cylinder must be of the indirect type with a
minimum capacity of 110 litres, conforming to
BS 1566 part 1.
Primary flow and return pipes should be 28mm
diameter. The cylinder should be installed at a
higher level than the appliance, and as close to it as
possible (the higher the cylinder the faster the
circulation). The flow and return pipes should not
be longer than 20ft each. Pipe runs should rise
continually from the boiler to the cylinder.
A radiator of approximately 25 sq.ft. should be
connected into the primary circuit, if installed in the
bathroom it provides a means of drying towels in
the summer.
Safety Vent Circuit
This circuit consists of a cold feed pipe, expansion
pipe, and expansion tank. The possibility that water
may boil can never be completely ruled out, and it
is therefore vital to ensure that cold water can be
supplied to the boiler and steam vented from it at all
times.
The expansion tank should have a capacity of at
least 7 % of the system's water capacity. The cold
water feed pipe should be at least 22mm diameter.
There must not be any shut off valves in the circuit.
Pipes should be run to avoid air locks. A safety
relief valve should be fitted to the expansion pipe
close to the boiler.
It is often possible, and is good practice, to utilise
the primary flow and return as part of the safety
circuit. The ball valve should have a copper ball.
The overflow pipe from the expansion tank should
be 28mm diameter copper. Pipes in unheated
spaces must be lagged.
28 Stratford Tf & Ti Multifuel Boiler Stoves
INSTALLATION