3M 5797A-MT Air Conditioner User Manual


 
5
78-8126-0432-6-A
3.0 Place Components on Cable
3.1 Slide one large cold shrink jacket tube onto
Cable X and one onto Cable Y with the loose
core ribbon ends going on the cable last, extending
toward the cable ends.
3.2 Slide a 3M
cold shrink splice body onto each
core of Cable X with the loose core ribbon
end going on the cable first, away from cable end.
3.3 Expand metallic shield sleeves and slide one onto
each core of Cable Y. Compress the ends of each
shield sleeve together next to the cable armor or
jacket, away from the prepared conductor ends.
3.4 For 1/0 through 3/0 AWG connectors, or
connectors with an O.D. between 0.51–0.76"
(13,0–19,3 mm): Slide the cold shrink adapter tube
with the WHITE CORE onto the insulation with the
loose core ribbon end going on first, away from the
cable end.
For 4/0 AWG through 350 kcmil connectors or
connectors with an O.D. between 0.68–1.07"
(17,3–27,2 mm): Slide the cold shrink adapter tube
with the RED CORE onto the insulation with the
loose core ribbon end going on first, away from the
cable end.
loose core ribbon end
splice body
loose core ribbon end
shield
sleeve
adapter tube
large jacket tube
loose core
ribbon end