Asked by Dave Hopstetter on 12/23/2008 2  Answers

ManualsOnline posted an answer 15 years, 11 months ago

The ManualsOnline team has found the manual for this product! We hope it helps solve your problem. Get the Manual Here
0 Blower motor works, fan works, unit sparks. I think it is either the curuit board or the gas valve. Please tell me how to verify. I have a ohm meter.
Was this answer helpful?
0 with ohm meter.......should have continuity between GV terms but w/some resistance. not zero resistance (shorted)...&no continuity between GV terms & body. (open) GV is OK.. If LP gas- check that out door reg. isn't frozen...too much press. & GV can't open.....check roll out switchs @ burners...press reset buttons or if auto reset-disconnect & ck continuity (should be closed)....PLEASE DISCONNECT ELECTRIC POWER BEFORE TESTING!!!!! If this doesn't help, I have more 411. filbertdesenex714@yahoo.com