0 Blower motor works, fan works, unit sparks. I think it is either the curuit board or the gas valve. Please tell me how to verify. I have a ohm meter.
Was this answer helpful?
0 with ohm meter.......should have continuity between GV terms but w/some resistance. not zero resistance (shorted)...&no continuity between GV terms & body. (open) GV is OK.. If LP gas- check that out door reg. isn't frozen...too much press. & GV can't open.....check roll out switchs @ burners...press reset buttons or if auto reset-disconnect & ck continuity (should be closed)....PLEASE DISCONNECT ELECTRIC POWER BEFORE TESTING!!!!! If this doesn't help, I have more 411. filbertdesenex714@yahoo.com