I am experiencing a problem w/furnace. Will not ignite. Motor and fan turn on and cycle. Hear clicking. Smell gas but burners will not light. 3 years ago the ignitor was replaced. Tech wrote replaced B4 on box. Can not locate ignitor to replace. Code 34 on LED. Any hsuggestions greatly appreciated.

Asked by Amedeo Piccinini on 11/08/2009 7  Answers

ManualsOnline posted an answer 15 years ago

The ManualsOnline team has found the manual for this product! We hope it helps solve your problem. Get the Manual Here
5 Try searaching 41-409 should be about $26 on line. $40 if you buy it from a local supply store. The ignitor is located on the right side under the burner. It sounds like that is the problem, in order to confirm put the furnace into a self check (ground test terminal for a few seconds) the ignigtor should glow white hot.
Was this answer helpful?
5 Try searaching 41-409 should be about $26 on line. $40 if you buy it from a local supply store. The ignitor is located on the right side under the burner. It sounds like that is the problem, in order to confirm put the furnace into a self check (ground test terminal for a few seconds) the ignigtor should glow white hot.
Was this answer helpful?
0 Try searaching 41-409 should be about $26 on line. $40 if you buy it from a local supply store. The ignitor is located on the right side under the burner. It sounds like that is the problem, in order to confirm put the furnace into a self check (ground test terminal for a few seconds) the ignigtor should glow white hot.
Was this answer helpful?
0 Try searaching 41-409 should be about $26 on line. $40 if you buy it from a local supply store. The ignitor is located on the right side under the burner. It sounds like that is the problem, in order to confirm put the furnace into a self check (ground test terminal for a few seconds) the ignigtor should glow white hot.
Was this answer helpful?
0 Try searaching 41-409 should be about $26 on line. $40 if you buy it from a local supply store. The ignitor is located on the right side under the burner. It sounds like that is the problem, in order to confirm put the furnace into a self check (ground test terminal for a few seconds) the ignigtor should glow white hot.
Was this answer helpful?
0 Thanks. It worked. The ignitor wa bad.
Was this answer helpful?