York 114 Water System User Manual


 
WATER SYSTEMS
Features
• 6 speed fan
• Cabinet factory tted
• Valve factory tted
• Electrical heater factory tted
• Thermal or modulating valve
• Service valve
Dimensions indicated next page
(1) Cooling capacities based on 7ºC EWT t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)
(2) Heating capacities based on 70ºC EWT t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)
(3) In cooling mode 2 rows
For other conditions contact York international
Technical features
YLVR - YLIVR
Model 110 112 114 216 218
Cooling capacity (1) 2 rows
W 832 1054 1493 2041 2356
Cooling capacity (1) 3 rows
W 913 1266 1790 2327 2714
Heating capacity (2) 1 row
W 1167 1691 2319 3029 3552
Pressure drop (3)
kPa 7 1.7 3.8 9 11.7
Power supply
V/Ph/Hz 230 / 1 / 50 + E
Sound power level (3)
dB(A) 49 50 53 53 55
Sound pressure level at 3 m
dB(A) 31 32 35 35 37
Water connections
inch 1/2 “
Thermostats
CSL00 (Built in)
CSR00 (Wall mounted)
Fan speed selector
CML00 (Built in)
CMR00 (Wall mounted)
Thermostat with manual fan speed and S/W
change over
CEL00 (Built in)
CER00 (Wall mounted)
Thermostat with manual fan speed and automatic
change over
CEL20 (Built in)
CER20 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over
CEL30 (Built in)
CER30 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over for modulating valve
Fan Coil Unit
LOW BODY (2 & 4 pipe system)
A complete range from 0.8 kW up to 2.7 kW
Selection
software