White Rodgers 24A34-3 Fan User Manual


 
24A34 Series
Fan/Heat Sequencers
INSTALLATION INSTRUCTIONS
DESCRIPTION
SPECIFICATIONS
The 24A34 Series Fan/Heat Sequencer gives the service tech-
nician a direct replacement for sequencing both fan and heat.
The terminal markings on the 24A34 sequencers are equivalent
to most other manufacturers’ types.
These sequencers may be wired in series, as shown in wiring
diagrams, to allow sequencing of one through seven element
furnaces.
CAUTION
!
To prevent electrical shock and/or equipment damage,
disconnect electric power to system, at main fuse or
circuit breaker box, until installation is complete.
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-4800C
Replaces 37-4800B
1050
TABLE NOTES:
M1-M2 and M3-M4 are always first switches to turn ON and last to turn OFF. All other switches are random ON and random OFF
24A34-14 Switch contacts designated F
1
- F
2
instead of M
1
- M
2
These contacts switch simultaneously
NOTE: Underwriters Laboratories requires a fan interlock circuit to insure the blower remains operating whenever more than one sequencer is used. The fan in-
terlock should be the M
1
/ M
2
contacts of the second or third sequencer. All M
1
/ M
2
contacts are wired to the blower motor so that any sequencer that is energized
will keep the blower ON.
Electrical Ratings - Single Load Contact Ratings (All Models)
VAC
Resistive (Non-Inductive) Motor Ratings (Inductive)
Pilot DutyWatts Amps Full Load Locked Rotor
120 3000 25.0 14.0A 72.0A 125 VA
240 6000 25.0 7.0A 42.0A 125 VA
480 6000 12.5 480 VA
Electrical Ratings - Single Load Contact Ratings (All Models)
Model
Number Timings Switches
Timings ON
Timings OFF
M1-M2 M3-M4 M5-M6 M7-M8 M9-M10 M1-M2 M3-M4 M5-M6 M7-M8 M9-M10
24A34-1
1 1 1-20
40-110
24A34-2
1 1 30-90
1-30
24A34-3
1 2 1-20 1-20
40-110 40-110
24A34-4
1 2 30-90 30-90
1-30 1-30
24A34-5
2 3 1-110 1-110 1-110
1-110 1-110 1-110
24A34-6
2 4 1-110 1-110 1-110 1-110
1-110 1-110 1-110 1-110
24A34-14 ➀➁
4 5 1-160 1-160 1-160 1-160 1-160
1-160 1-160 1-160 1-160 1-160
24A34-15
1 1 1-60
75-95