Watlow Electric SERIES146 Thermostat User Manual


 
1 Watlow Series 146 User’s Manual
Series 146
User’s Manual
Temperature Regulator
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com
Registered Company
Winona, Minnesota USA
TOTAL
3 Year Warranty
CUSTOMER
SATISFACTION
$5.00 Made in the U.S.A.
0600-0004-0010 Rev D
December 2001
Supersedes: 0600-0004-0010 Rev C
(2089)
Control Mode
High or low limit, factory selectable
Manual or automatic reset on power loss, factory selectable
Latching alarm with manual reset on over or under temperature
Internal and/or customer supplied external reset switch
Operator Interface
LED indication of output status
Dial scale calibrated to compensate for sensor
non-linearities
Integral or remote set point
Dual temperature scale (°C and °F)
Fixed set point
Manufactured to specified value
Input
Thermocouple or platinum RTD available
Thermocouple with automatic cold junction compensation
Thermocouple may be isolated or grounded
Thermocouple and RTD break protection de-energizes output
2- or 3-wire RTD input, 100@ 0°C calibrated for 0.003850/
°C curve
Output
Electromechanical relay, 8A, Form C, SPDT: 8A @ 240VÅ resis-
tive, 8A @ 28VÎ (dc) resistive, 275VA pilot duty rated
Accuracy
Adjustable Set Point, integral or remote
Calibration accuracy: ±1% of span, at 25°C ± 3°C (77°F ±5°F)
ambient and rated line voltage ± 1%
Set point accuracy: ±3% of dial scale
Accuracy span: 540°C (1000°F) minimum
Fixed Set Point
Calibration accuracy: ±6°C/±10°F of setting, at 25°C ±3°C (77°F
±5°F) ambient and rated line voltage ±1%
Temperature Stability
Thermocouple: Typically 9µV/°C ambient (5µV/°F ambient) input
referenced
RTD: Typically 0.2°C/°C ambient (0.2°F/°F ambient)
Voltage Stability
±0.01% of span (min. span of 540°C or 1000°F) per % of rated
line voltage
Agency Approvals
CE: EN61010 - Safety
EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2
873, File #E43684
to C22.2 No. 24, File #E43684
Approved for use in commercial cooking applications
FM Class 3545, File J.I. 3007307
Terminals
Captive screw, cage clamp connection, 4 mm (0.155 in.) max.
width screwdriver blade, 30 to 14-gauge wire
Mounting
DIN rail, DIN EN50022, 35 mm x 7.5 mm
Sub-panel flush mounting
Power
24V~, +10%/-15%, 50/60 Hz
120V~, +10%/-15%, 50/60 Hz
230V~ to 240~, +10%/-15%, 50/60 Hz
10VA maximum power
Operating Environment
0 to 55°C (32 to 131°F)
0 to 90% RH, non-condensing
Storage temperature: -20 to 85°C (-4 to 185°F)
Dimensions
Width: 60 mm (2.28 in)
Height: 115 mm (4.45 in)
Depth: 100 mm (3.89 in)
Weight
0.3kg (0.7 lb.)
UL
®
is a registered trademark of Underwriter’s Laboratories, Inc.
Note: Specifications subject to change without notice.
Specifications
The Watlow Series 146 is a DIN rail mount, tempera-
ture regulating controller with a thermocouple or RTD
sensor input. The DIN rail mounting offers quick and easy
installation with the use of simple hand tools. The con-
troller may also be flush mounted.
The Series 146 is designed to meet the needs of a
wide range of safety applications. Factory selectable
options include high or low control mode with either
manual or automatic reset on power loss.
The Series 146 has an LED for output status
indication and can be ordered with an integral or remote
adjustable set point, or a fixed set point.
General Description