Vanguard Heating VMH10TNB Indoor Fireplace User Manual


 
6
107031
VENT-FREE NATURAL GAS COMPACT FIREPLACE
VMH10TNB
®
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height = ____________________ cu. ft. (volume of space)
Example:
Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling height) = 1792 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.
2. Multiply the space volume by 1000 Btu/Hr per 50 cubic feet to determine the maximum Btu/Hr the space can support.
_____________________(volume of space) x 1000 Btu/Hr = (Maximum Btu/Hr the space can support) 50 Cubic Feet
Example:
1792 Cubic Feet (volume of space) x 1000 Btu/Hr ÷ 50 Cubic Feet= 35,840 Btu/Hr. This is the maximum Btu/Hr the
space can support.
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace ________________________ Btu/Hr
Gas water heater* ________________________ Btu/Hr
Gas furnace ________________________ Btu/Hr
Vented gas heater ________________________ Btu/Hr
Gas fireplace logs ________________________ Btu/Hr
Other gas appliances* + ________________________ Btu/Hr
Total = ________________________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
35,840 Btu/Hr (maximum the space can support)
40,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space
or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the
National Fuel Gas Code, ANS Z223.1, Section 5.3
or applicable local codes.
AIR FOR
COMBUSTION AND
VENTILATION
Continued
Example:
Gas water heater 30,000 Btu/Hr
Vent-free fireplace + 10,000 Btu/Hr
Total = 40,000 Btu/Hr