Trane RAUC-C40 Air Conditioner User Manual


 
SS-SVX09A-EN 61
Installation
Outside Air Thermostat (5S57 Field Provided)
The setpoint for the outside air thermostat is based upon the working ambient selected when the
unit was ordered. A Zero (“0”) in the 11th digit of the model number indicates the system is
designed for standard ambient operation of 40ºF and above. A One (“1”) in the 11th digit of the
model number indicates the system is designed for low ambient operation of 0ºF and above.
Therefore, select a thermostat with the appropriate operating range based on the unit
specifications.
ƽ WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Refer to the field connection diagram for the specific connection points inside the remote panel.