Trane RAUC-C40 Air Conditioner User Manual


 
SS-SVX09A-EN 51
Installation
Controls using 24 VAC
ƽ WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring, refer to Figure 3 to Figure 8 for the electrical access
locations provided on the unit and Table 9 for AC conductor sizing guidelines, and;
1. Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit’s termination point does
not exceed three (3) ohms/conductor for the length of the run.
NOTICE
Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient
AC voltage supply.
3. Be sure to check all loads and conductors for grounds, shorts, and miswiring.
4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
Typical Low voltage components may include:
zone thermostat wiring (AC & DC wiring);
system control switch wiring (VAV units);
night setback relay wiring (VAV units);
economizer actuator circuit wiring (VAV units);
discharge air sensor wiring (VAV units);
chilled water temperature sensor (EVP units);
jumpers for hot gas bypass operation.
Controls using DC Analog Input/Outputs
ƽ WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring between the unit and components utilizing a DC analog
input\output signal, refer to Figure 3 to Figure 8 for the electrical access locations provided on the
unit.
Table 9. AC Conductors
Distance from
Unit to Control
Recommended
Wire Size
000 - 460 feet 18 gauge
461 - 732 feet 16 gauge
733 - 1000 feet 14 gauge