The Sentry controller is the heart of the Sentry Gas Risk
Management system. It is a microprocessor based sys-
tem that performs functions including management of the
sensor modules, management of alarm relays and inter-
face with the user via the front panel display, printer out-
put, Modbus digital communication, alarm indicators and
relay outputs.
Sentry system two-way communication between the sen-
sors and the controller results in the capability to perform
one-person calibration and diagnostic checks from the
controller. The user-friendly front panel includes a large
display of the gas concentration and sensor number. Vari-
ous scan modes are available to meet the user’s specific
monitoring needs. A separate 2-line alphanumeric dis-
play provides more detailed information including sensor
data, error messages and menu prompting for calibration
and set-up.
A series of alarm LEDs instantly inform the user of alarm
status on any of the eight sensors interfaced to the con-
troller. These LEDs are solid for low alarm and flashing for
high alarm. A trouble LED warns that one of 120 diagnos-
tic checks has detected a problem. More information about
the trouble will be displayed on the alphanumeric display.
A calibrate/change LED indicates that calibration or con-
figuration change is being performed on at least one sen-
sor. The remaining sensors will remain on-line providing
continuous protection.
The Sentry keypad, together with the user-friendly menu
on the alphanumeric display, guides the user through set-
up, calibration and maintenance of the Sentry system.