Modular Boiler Submittal Data
LZDF SERIES—Dual Fuel/Steam
A Caravan modular boiler system con-
sists of two or more compact boilers that
offer significant advantages in terms of
installed cost, efficiency and reliability.
Caravan systems are based on step-firing
just enough modules to meet heating
demands. LZDF systems are available in
620,000 to multi-million Btuh gross input.
For additional information, see Caravan
Engineer
ing Manual, pub. C-30.
Standard Equipment
One per module unless otherwise noted
Pre-assembled heat exchanger with
insulated jacket.
Dual fuel gas/oil burner with oil valve, gas
regulator, gas valve, flame safeguard
with UV scanner and on-off fuel transfer
switch (unmounted). Gordon-Piatt burner
model #S4.1-GO has intermittent gas
pilot to light oil and/or gas main flame.
Module pressure gauge and siphon
(unmounted).
System pressure gauge and siphon
(unmounted, one per system).
* Light oil, 140,000 Btu per gallon. ‡ Based on 150 Btuh per square foot E.D.R.at 170°F average water temperature.
† Net ratings are based on piping and pick-up allowance of 1.33. Slant/Fin
should be consulted before selecting a boiler for installation having unusual § Modules in excess of 8 are piped in parallel in two or more banks.
piping and/or pick-up requirements
. For higher elevations, input may need to
be reduced.
LZDF-600-2-5 2 620 500 83.30 375 1563 14.9 4.30 602 500 85.90 375 1563 14.9 21.4 1506 3"
LZDF-750-2-6 2 750 592 83.20 444 1850 17.7 5.20 728 592 85.80 444 1850 17.7 25.2 1710 3"
LZDF-850-2-7 2 798 620 82.90 466 1946 18.6 6.00 840 674 85.50 506 2108 20.1 29.0 1918 3"
LZDF-900-3-5 3 930 750 83.30 563 2346 22.4 6.40 896 750 85.90 563 2346 22.4 32.1 2259 3"
LZDF-1100-3-6 3 1125 888 83.20 666 2775 26.5 7.80 1092 888 85.80 666 2775 26.5 37.8 2565 5"
LZDF-1300-3-7 3 1197 930 82.90 699 2917 27.9 9.00 1260 1011 85.50 758 3158 30.2 43.5 2876 5"
LZDF-1700-4-7 4 1596 1240 82.90 932 3888 37.2 12.00 1680 1348 85.50 1018 4242 40.3 58.0 3834 6"
LZDF-2100-5-7 5 1995 1550 82.90 1165 4963 46.5 15.00 2100 1685 85.50 1298 5408 50.3 72.5 4794 6"
Module pressure re-
lief valve, ASME
(unmounted) 15 psi.
Double swing draft
regulator (unmounted).
Flue brush.
Drain cock (unmounted).
Water level sight glass
(unmounted).
Standard Equipment
Dual fuel changeover thermostat.
Internal tankless heaters.
Two-stage fuel pump in place of one-
stage fuel pump.
ASME Package—includes:
67 Low water cutoff (one per module)
PA404A Pressure control (one per mod.)
67M Low water cutoff (one per system)
L4079B Manual reset pressure
Ratings
Model No.
No.
of
Htg.
Mods
Input
MPH
Gross
Output
MPH
†
Comb.
Efficiency
Net
Output
MPH
†
Sq. Ft.
Steam
‡
Horse-
power
Firing
Rate
GPH*
Input
MPH
Gross
Output
MPH
Comb.
Efficiency
Net
Output
MPH
†
Sq. Ft.
Steam
‡
Horse-
power
Boiler
W
ater
Content
(gal)
W
eight
with
Water
Recom-
mended
Header
Size
I=B=R
RATINGS FOR GAS RATINGS FOR OIL
I=B=R
Dual Fuel Caravan ratings and dimensions/steam models–LZDF Series
®