Sanyo CHDX09053 Heat Pump User Manual


 
CHDX09053
Heat Pump: 8 tons VRF Outdoor Unit
Capacities
Cooling: Btu/h
Power Input: KW
Heating: Btu/h
Power Input: KW
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
Outdoor: °F DB
Pipe Length (feet):
Level Difference (feet):
Heating Mode Nominal Conditions
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length (feet):
Level Difference (feet):
Operating Range
Cooling: °F DB:
Heating: °F DB:
Compressor
Quantity/Type:
Capacity Control Range:
Fan
Quantity/Type:
Fan Motor Output (KW):
Power Supply
V/PH/Hz.
Minimum circuit Amps (MCA): Amps
Max. Overcurrent Protection (MOCP):
Weight (lbs):
Refrigerant:
Coil
Coil Face Area (sq. ft.):
Number of Rows:
Protection Devices
High Pressure Switch:
Overcurrent (CT Method):
Crankcase Heaters (W):
External Finish:
95,500
7.9
107,500
7.75
80/67
95
25
0
70
47/43
25
0
Yes
Yes
25 + 32
208-230 / 3 / 60
38
50
1 Propeller
0.7
14 to 109
-4 to 59
1 Inverter driven rotary & 1 fi xed speed scroll
10-100%
650
410A
Electrostatic Powder Coating
22.5
ECO-i
Submittal Data
4
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit #:
Drawing #:
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also avilable
Print Form