-
1-
SANYO AIR CONDITIONING PRODUCTS
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
SPECIFICATIONS - SECTION 15700
Covers Sanyo System Models > 12RS11, 12RLS11 (See plans for specified models & details)
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - RECESSED CEILING MOUNT
1) GENERAL SPECIFICATIONS
Furnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s) consisting of an
indoor recessed ceiling mounted evaporator/blower section & matching outdoor condensing
section. System(s) shall bear the ARI label showing that the system(s) is ARI 210 or 240 & 270
Certified. Systems shall be listed by ETL Testing Laboratories and bear the ETL label. Matching
systems shall meet or exceed the minimum, Federally mandated Seasonal Energy Efficiency
Rating (SEER) of 10, as certified by the ARI testing programs. System(s) indoor & outdoor units
will operate at sound levels equal to or below specified system(s) (see plans). Installation &
Owners Manuals shall be provided with each system.
Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper
tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on
both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.
System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-
charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor
units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),
shall be sized, installed & grounded by the installer in conformance with the National Electrical
Code (N.E.C.), local codes, as well as, manufacturer’s instructions.
System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote
controller with LCD display that provides access to all system functions, and transmits room
conditions & programs to the indoor microprocessor every 3 minutes. Infrared remote controller
shall be capable of operating system mounted up to 26’ from the indoor section, according to
manufacturer’s recommendations & instructions. System(s) shall have the capability of continuous
operation in the case of a lost or damaged remote controller, utilizing a factory installed, integral
manual switch in conjunction with the system microprocessor.
System Infrared Remote Controller Functions will include: system mode selection,
programmable temperature control, 24 hour programmable timer, automatic three (3) speed indoor
fan speed control, constant fan speed selection, night setback mode, user selectable room
temperature sensor located on either infrared remote controller or indoor unit, multiple system
control using a single controller.
System Features will include: Sanyo high efficiency, rotary compressor, with suction line
accumulator, a strainer, cap tube refrigerant control, indoor coil freeze protection, built-in auto
restart after power failure, short cycle time delay, low ambient cooling operation to zero degrees