A.11: Technical Data For Service Personnel – SIAM Compressors – R134a
Parameters 150-08ACW-134 270 & 340-11AC3-134
340TIH-134
340-17ACW-134
Superheat setting 1.5Turn(F.Close) 3.5 Turns(7 Turns ) F..Open 3.5Turns(7Turns) F.Open
TX valve + orifice size TI-E 2# TEN2 # 3(AAE 2MC) TEN2 # 4
Winding Resistance @20℃ C-R: 2.13Ω, C-S: 3.91Ω C-R: 0.96Ω, C-S: 1.77Ω
Run Capacitor 30μF (+10, -5%) 370 VAC 30μF (+10, -5%) 370 VAC 60μF (+0, -15%) 400 VAC
Rated power supply 220-240VAC, 50Hz 220-240VAC, 50Hz 220-240VAC, 50Hz
Rated circuit breaker 1Φ, 15A 1Φ, 15A 1Φ, 15A
De-ice control setting On-5℃, Off + 8℃ (Timed De Icing) On - 5℃, Off + 8℃ (Timed De Icing) On-5℃, Off + 8℃ (Timed De Icing)
Liquid injection capillary Eyre: ID 1.1mm x 1.5m Eyre: ID 1.1mm x 2.9m ID 1.1mm x 2m
Liquid injection thermostat On at 85℃, Off at 75℃ On at 85℃, Off at 75℃ On at 85℃, Off at 75℃
Water temperature setting 55℃/5℃ (Del. ≥60℃) 55℃/5℃ (Del. ≥60℃) 55℃/5℃ (Del. ≥60℃)
Refrigerant charge 1650g 1850g 2650g
Thermal cut-out setting 105℃, manual reset 105℃, manual reset 105℃, manual reset