Page12
7014-179D
December 16, 2011
R
CB 1200 Pellet Stove
Improperinstallation,adjustment,alteration,serviceor
maintenancecancauseinjuryorpropertydamage.Refer
totheowner’sinformationmanualprovidedwiththisappli-
ance.Forassistanceoradditionalinformationconsulta
qualiedinstaller,serviceagencyoryourdealer.
WARNING
Thechartwillhelpyouindeterminingproper
ventingsizeaccordingtotheequivalentfeetof
pipecalculatedaboveandthealtitudeabovesea
levelofthisinstallation.Figure 12.2.
Locatethecalculatedequivalentfeetofpipeon
theverticalleftsideofthechart.Movetothe
righthorizontallyonthechartuntilyoureach
youraltitudeabovesealevel.
Ifyoufallbelowthediagonalline,3or4inch(76
to102mm)pipemaybeused.Ifitisanywhere
abovethediagonalline,a4inch(102mm)diam-
eterpipeisrequired.
Thechartrevealsthata90°elbowis5timesas
restrictivetotheowof exhaustgasesunder
positivepressureas1footofhorizontalpipe,and
afootofhorizontalpipeistwiceasrestrictiveas
afootofverticalpipe.
D. Pipe Selection Chart
Thetablebelowcanhelpyoucalculatetheequivalentfeet
ofpipewhichisamethodusedtodeterminepelletventsize.
Figure 12.1.
C. Equivalent Feet of Pipe
Example of 3 Elbow-Rear Vent Termination Calculaton
Figure 12.1
FireRisk.
DoNOTpackinsulationorother
combustiblesbetweenrestops.
• ALWAYSmaintainspeciedclearances
aroundventingandrestopsystems.
• Installrestopsasspecied.
Failuretokeepinsulationorothermaterial
awayfromventpipemaycausere.
WARNING
3 in. or 4 in. (76mm or 102mm) Diameter Pipe
Equivalent Pipe
Length In Feet
ALTITUDE IN THOUSANDS OF FEET
0
20
30
1 2 3 4 5 6 7 8 9 10
4 in. (102mm) Diameter Pipe Only
10
Example 1
Example 2
Figure 12.2
3 ft
(914mm)
2 ft (609mm)
2 ft (609mm)
2 ft (609mm)
Pellet Venting
Component
# of
Elbows
Feet of
Pipe
Multipled
By
Equivalent
Feet
Components
Equivalent Feet
90
o
ElboworTee
3 X 5 15
45
o
Elbow
X 3
HorizontalPipe
7 X 1 7
VerticalPipe
2 X 0.5 1
TotalEquivalentFeet 23
Note:Thisisagenericexampleandisnot
intendedtorepresentanyspecicfueltype.
Example 1:Iftheequivalentlengthofpipeis23feet
(7m)withaltitudeof8,000feet(2438m)youmustuse
4inch(102mm)diametertype“L”or“PL”vent.
Example 2:Iftheequivalentlengthofpipeis12feet
(3.7m)withaltitudeof6,000feet(1829m)youmay
use3or4inch(76to102mm)diametertype“L”or
“PL”vent