PVI Industries PV 6127b Water Heater User Manual


 
PV 6127b 6/01 1
SPECIFICATION FOR DOMESTIC WATER HEATERS
Atmospheric Combustion, Gas-Fired Water Heaters
with Polymer-Lined Storage Tanks
Furnish and install atmospheric gas water heater(s) as manufactured by PVI Industries, L.L.C.
of Fort Worth, Texas. Supply quantities and model numbers as indicated on the plumbing schedule.
Gas and Electrical Consumption
The water heater will operate at 80% thermal efficiency. The water heater will comply with paragraph 7.2.4.4, the
thermal efficiency, the standby loss, and all other requirements of ASHRAE 90.1-1999.
Pressure Vessel and Heating Surfaces
The water heater will be a vertical fire tube design that is constructed and stamped in accordance with Section IV,
Part HLW of the ASME code. Both the storage and heating sections of the water heater will be National Board
Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure. The fireside of
the heating surfaces will be of boiler-grade steel. The waterside of the heating tubes will be sealed in copper. The
heating tubes will be rolled, beaded, and seal welded into the tube sheets. The combustion side of the tube sheet will be
insulated by a layer of ceramic fiber that will protect the tube sheet from both thermal stresses and failure that can result
from the accumulation of scale and precipitants.
Tank Lining
The lining will:
be applied only after the tank is completely fabricated and all welding is completed.
consist of multiple applications of high-temperature fluoropolymer.
be third-party tested to and comply with NSF 61standard.
be continuous and nonporous with no interruptions or discontinuities.
require no
sacrificial anode rods for protection.
Burner and Venting
Combustion will be provided by an atmospheric burner with a gas train meeting the following agency requirement for
the input specified:
___ UL (standard) ____ FM ___ IRI ___ Other ______________________
Water heater will be a category 1, non-condensing appliance. It will be UL-listed for use with non-pressurized, type
B venting material.
Safety Controls
As a minimum
, the heater will be equipped with the following:
electronic flame monitoring
two immersion operating thermostats
an immersion temperature limiting device
an ASME- or AGA-rated temperature and pressure relief valve
and options as selected on form PV 6071
(continued)