PVI Industries 20 P 125A-MXS Water Heater User Manual


 
LOW NOx MAXIM • PACKAGED GAS WATER HEATER
POLYSHIELD
®
POLYMER-LINED STORAGE TANK
125 GALLON TANK SERIES
MODEL NUMBER
20 P 125A-MXS 27 P 125A-MXS 40 P 125A-MXS
GPH Recovery at 40° to 120° F 245 330 490
GPH Recovery at 40° to 140° F 195 260 390
Input Btu/h 199,000 270,000 399,000
Minimum gas inlet pressure – " W.C. 5.5 5.5 5.5
A Cold Inlet - NPT 2 2 2
B Hot Outlet - NPT 2 2 2
C Drain - NPT 1 1 1
D I - Beam Skids 3 X 34-1/2 3 x 34-1/2 3 x 34-1/2
E Overall Depth 45 45 45
F Overall Height 75 75 82
G Flue Outlet Diameter 5 6 7
H Gas Inlet - NPT 1/2 3/4 3/4
J Motor HP 120 V, 1Ø, 60 Hz. 1/6 1/6 1/6
Motor Amps 1.75 1.75 1.75
L Height to Outlet 65 65 73
M Height to Inlet 28 28 36
Approx. Shipping Weight - lbs 1020 1070 1130
Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant.
1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3” NPT Handhole
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see Form # PV6377.
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6378 02/05 (800) 784-8326 www.pvi.com
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC PRESSURE: 9" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE
VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE
UNDER "FAN-ASSISTED".
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.