PVI Industries 1500PHE125A-TPO Water Heater User Manual


 
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
"J" dimension is for the burner housing only.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form PV 6006.
Model
Number
Recovery gph
Input
Btu/h
Dimensions
(inches)
Blower
Motor
Shipping
Weight
lbs
40°- 120°F 40°- 140°F A B J HP Volt/Ph/Amps
250 PHE 125A-TPO 250 200 199,000 24 4 17 1/3
115/1/8
970
500 PHE 125A-TPO 500 400 399,000 24 5 17 1/2
115/1/10
990
750 PHE 125A-TPO 750 600 600,000 27 6 17 1/2
115/1/10
1070
1000 PHE 125A-TPO 1000 800 800,000 27 8 17 1/2
115/1/10
1110
1250 PHE 125A-TPO 1250 1000 1,000,000 27 8 17 1/2
115/1/10
1350
1500 PHE 125A-TPO 1500 1200 1,200,000 27 8 17 1/2
115/1/10
1360
Gph
#2 Oil
1.4
2.8
4.3
5.7
7.2
8.6
TURBOPOWER
®
OIL PACKAGED WATER HEATER
POLYSHIELD
®
POLYMER-LINED STORAGE TANK
TANK SERIES 125 GALLONS HORIZONTAL
PV 5458 04/05
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
(800) 784-8326
(817) 335-9531 www.pvi.com
Product is patented in the U.S., Canada, and Mexico.
VENTING REQUIREMENTS
-.02" TO -.06" W.C. (NEGATIVE PRESSURE)
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED
UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER SIZING, CONSULT VENTING SUPPLIER.
STANDARD ELECTRICAL REQUIREMENTS
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL
REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR
AN OPTIONAL CONTROL CIRCUIT TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN
AND SPECIFICATION WITHOUT NOTICE.